Air Distribution Performance According to the Gap Opening of a Temperature Controlled Diffuser

냉난방 온도감지 디퓨져의 간극변화에 따른 기류분포 특성

  • Han Hwataik (School of Mechanical and Automotive Engineering, Kookmin University) ;
  • Shin Min-Woo (Graduate School of Mechanical Engineering, Kookmin University) ;
  • Yom Chol-Min (Graduate School of Mechanical Engineering, Kookmin University) ;
  • Choi Sun-Ho (Graduate School of Mechanical Engineering, Kookmin University)
  • Published : 2006.02.01

Abstract

This study has been conducted in order to develop a temperature-controlled round pan diffuser with variable-openings. Flow visualization was performed to investigate the airflow patterns according to gap openings. The velocity profiles were measured using an omni-directional anemometer for two cases, i.e. a horizontal and a vertical discharge conditions. Numerical simulation also confirms there is a narrow range of gap openings where a horizontal discharge shifts to a vertical discharge. The air distribution performance index increases abruptly when the air discharge shifts from vertical to horizontal direction.

Keywords

References

  1. Engel, J. A. and Kirkpatrick, A. T., 1993, Experimental determination of the airflow performance of a variable-area radial diffuser, ASHRAE Transactions, Vol. 99, No.2, pp. 759-769
  2. Kirkpatrick, A. T. and Knappmiller, K. D., 1996, The ADPI of cold air jets in an enclosure, ASHRAE Transactions, Vol. 102, No.1, pp. 3-9
  3. Kashirajima, Y., Sugiura, T., Takahashi, M., Sugihara, Y. and Ooshima, N., 2002, Experimental study of indoor thermal environmental for cold air distribution systems using various air outlets, ASHRAE transactions, Vol. 108, No. 2, pp. 16-22
  4. ASHRAE, 1991, Method of testing for rating the performance of air outlets and inlets, ANSI! ASHRAE Standard 70-1991
  5. ASHRAE, 20m, ASHRAE Handbook-Fundamentals, Chapter 32, Space Air Diffusion
  6. Oh, Y. J., Jung, D. W. and Shim, J. E., 1998, An experimental study on the energy consumption according to diffuser performance evaluation, SAREK, pp. 441-446