DOI QR코드

DOI QR Code

2단 응축 히트펌프 온수시스템의 사이클 해석 및 성능분석

Performance of Heat Pump Water Heater with Dual Condenser

  • Ryou, Y.S. (National Institute of Agricultural Engineering) ;
  • Kim, Y.J. (National Institute of Agricultural Engineering) ;
  • Kang, G.C. (National Institute of Agricultural Engineering) ;
  • Paek, Y. (National Institute of Agricultural Engineering) ;
  • Yun, J.H. (National Institute of Agricultural Engineering) ;
  • Kang, Y.G. (National Institute of Agricultural Engineering) ;
  • Lee, H.M. (National Institute of Agricultural Engineering)
  • 발행 : 2006.10.25

초록

The heat pump water heater developed in this research consisted of one evaporator, one compressor, 1st condenser, 2nd condenser, one expansion valve, one water tank, one recirculation circuit and etc. The performance of heat pump water heater was tested and analyzed. The quantities of output water changed linearly from 2380 to $660{\ell}/h$, and the output water temperature changed curvedly from 29.9 to $44.5^{\circ}C$ when the opening rate of recirculation valve changed from 0 to 100%. The COP of heat pump water heater increased from 3.0 to 3.8 when the quantities of output water changed from 660 to $2380{\ell}/h$. When the temperature distributions of water tank were measured during 50 minutes after turning on the heat pump, the temperature stratification by the level appeared apparently. When the inlet water temperature changed from 30 to$50^{\circ}C$, the output energy of heat pump hardly changed. The surface area of double pipe heat exchanger changed from 0.429 to $6.254m^2$ when the compressor capacity increased from 1.0 to 50.0 PS.

키워드

참고문헌

  1. Gregory, S. B. 1999. Heat pump apparatus for heating liquid. United States Patent Number 5,984,198
  2. John, T. D. 1999. Heat pump water heater and storage tank assembly. United States Patent Number 5,946,927
  3. Edwin, L. G. 1996. Heat pump hot water heater. United States Patent Number 5,573,192
  4. Glen, P. R. 1996. Fast recovery circuit for heat pump water heater. United States Patent Number 5,495,551
  5. Ryou, Y. S., Y. J. Kim, G. C. Kang, Y. Paek, J. H. Yun and G. J. Lee. 2001. Performance of an advanced heat pump water heater with pre-condenser. Proceedings of the KSAM 2001 Winter Conference 6(1): 117-123