Development of Delta-I ground fault Protective Relaying Scheme for DC Traction Power Supply System

비접지 DC 급전시스템에서의 Delta-I 지락보호계전 시스템

  • Published : 2006.12.01

Abstract

In DC tracking power supply system, ground faults are currently detected by the potential relay, 64P. Though 64P relay detects ground fault, it cannot identify the faulted region which causes long traffic delays and safety problem to passengers. A new ground fault protective relay scheme, ${\Delta}I$ ground fault protective relay, that can identify the faulted region is presented in this paper. In ${\Delta}I$ ground fault protective relaying scheme, ground fault is detected by 59, overvoltage relay, which operates ground switch installed between the negative bus and the ground. It preliminarily chooses the faulted feeder after comparing the current increases among feeders and trips the corresponding feeder breaker. After some time delay, it then recloses the breaker if it finds the preselected feeder is not the actual faulted feeder. Whether or not the preselected feeder is the actual faulted feeder is determined by checking the breaker trip status in the neighboring substation in the direction of the tripped breaker. If the corresponding breaker in the neighboring substation is also tripped, it finally judges the preselected feeder is actually a faulted feeder. Otherwise it recloses the tripped breaker. Its algorithms is presented and verified by EMTP simulation.

Keywords

References

  1. Toru Aihara, Shin-ichi Hase, Hiroaki Morimoto, 'Development of a DC feeding bus ground fault detection system for railway substation', 2005한중일 기술교류회, June 2005
  2. 정상기, 정락교, 조흥식, 이안호, 권삼영, 'DC 급전시스템의 지락보호계전시스템 개발', 전기학회논문집, Vol.54A, Sep. 2005
  3. 일본철도전화협회, 급전회로보호시스템, P9