초록
The existing ULTC operation control strategy based on the measured data deteriorates the voltage compensation capability making the efficient corresponding to the load variation difficult by following the fixed load center point voltage. Accordingly, this paper proposes a new on-line fuzzy ULTC controller based on the designed multiple load center points which can improve the voltage compensation capability of ULTC and minimize voltage deviation by moving in real-time the load center point according to the load variation to an adequate position among the multiple load center points designed using the clustering technique. The Max-Min distance technique is adopted as the clustering technique for the decision of multiple load points from measured MTr load current and PTr voltage, and the minimum distance classifier is adopted for the decision of fuzzy output membership function. To verify the effectiveness of the proposed strategy, Visual C++ MFC-based simulation environments is developed. Finally, the superiority the proposed strategy is proved by comparing the fuzzy ULTC operation control results based on multiple load center points with the existing ULTC operation control results based on fixed load center point using the data for three day.