Analysis of ELF Magnetic Field Reduction Factor of Electric Power Transmission Line

송전 선로 극저주파 자기장 저감지수(FRF) 특성 해석

  • Published : 2006.11.30

Abstract

This paper examined electric power transmission line models of reducing ELF(Extremely Low Frequency) magnetic field and analyzed the effects about models. In this research, FRF(Field Reduction Factor) of various models reducing magnetic field were analyzed compared to the horizontal 154 kV transmission line. As a result, the reduction ratio of magnetic field was almost proportioned to the compaction of phase-to-phase distance, and in case of diamond model and transposed model, magnetic field was able to be reduced nearly 50 %. It was analyzed that the magnetic field reduction ratio of triangle model was about 33 % and the magnetic field reduction ratio of split model was able to be reduced to 50 %. Especially, the magnetic field reduction ratio of multi split model could be reduced to 80 %.

본 연구는 송전 선로 여러 가지 유형의 극저주파 자기장 저감 적용 모델을 조사하고 그 효과를 분석하였다. 본 연구에서는 154 kV 수평 배열 송전 선로를 기본으로 하여 적용 가능한 다양한 자기장 저감 모델에 대하여 적용시 얻게 되는 자기장 저감지수(Field Reduction Factor)를 검토하였다. 그 결과 compact 모델 채용시에는 상간거리 compact화 비율과 자기장 저감지수가 거의 비례하였으며, diamond 모델 및 transposed 선로 배치의 경우는 50 %에 근접한 자기장 저감이 가능하였다. 배전 선로에 적용이 가능한 삼각형 배열은 33 % 정도, 2회선 split는 50 % 정도 저감 효과가 나타나는 것으로 분석되었으며 수평 multi split 모델의 경우는 80 %까지 자기장 저감을 얻을 수 있었다.

Keywords

References

  1. Electric Power Research Institute, 'Transmission line reference book 345 kV and above', 2nd Ed. chap. 8, 1982
  2. CRIEPI, 'Electrical design handbook of 187kV-1, 100 kV transmission lines', 1987
  3. V.S. Rashkes, R. Lordan, 'Magnetic field redection methods : Efficiency and cost', IEEE Trans. on Power Delivery, vol. 13, no. 2, pp. 552-559, Apr. 1988 https://doi.org/10.1109/61.660928
  4. W. T. Kaune, L. E. Zaffanella, 'Analysis of magnetic fields produced far from electric power lines', IEEE Trans. on Power Delivery, vol. 7, no. 4, pp. 2082-2091, 1992 https://doi.org/10.1109/61.157011
  5. EPRI, 'Magnetic field management for overhead transmission lines: Potential options for low field designs', TR-104413, Sep. 1995
  6. A. R. Memari, W. Janischewskyj, 'Mitigation of magnetic field near power lines', IEEE Trans. Power Delivery, vol. 11, no. 3, pp. 1577-1586, 1996 https://doi.org/10.1109/61.517519
  7. Per Pettersson, 'Principles In transmission line magnetic field reduction', IEEE Trans on Power Delivery, vol. 1, no. 3, Jul. 1996
  8. Sung Ho Myung, 'Analysis of magnetic field distribution around electric power facilities', CRIEPI/KEPRI/KERI Joint Workshop on Electric & Magnetic Field Effects, May 1999
  9. 명성호, '송전 선로 주변의 3차원 자기장 및 인체 유도 와전류 계산', 대한전기학회 논문지, 51(9), 2002년 9월