Correlation of Critical Air Temperature for Frost Delay on a Cold Plate

냉각면 평판에서 착상 지연을 위한 임계공기온도 상관식

  • 김정수 (한양대학교 대학원 기계공학과) ;
  • 김유일 (한양대학교 대학원 기계공학과) ;
  • 김욱중 (한국기계연구원 에너지기계연구센터) ;
  • 이관수 (한양대학교 기계공학부)
  • Published : 2006.12.01

Abstract

This paper examines the critical air temperature at which frost formation does not occur on a cold plate in order to improve the efficiency of a heat pump. The critical air temperature on test points is obtained from numerical analysis and a correlation of the critical air temperature is derived as a function of frosting factors (air absolute humidity, air velocity, and cold plate temperature) by least square method. Experiments are carried out to verify the correlation proposed in this study, and the prediction obtained with the correlation agrees well with the experimental data. Based on the correlation, we propose the non-frosting regions according to frosting factors.

Keywords

References

  1. Seker, D., Karatas, H. and Egrican, N., 2004, 'Frost Formation on Fin-and-tube Heat Exchangers, Part I - Modeling of Frost Formation on Fin-and-tube Heat Exchangers,' Int. J. Refrigeration, Vol. 27, pp. 367-374 https://doi.org/10.1016/j.ijrefrig.2003.12.003
  2. Kondepudi, S. N. and O'Neal, D. L., 1993, 'Performance of Finned-tube Heat Exchangers Under ?Frosting Conditions. I. Simulation Model,' Int. J. Refrigeration, Vol. 16(3), pp. 175-180 https://doi.org/10.1016/0140-7007(93)90045-A
  3. Yang, D. K., Lee, K. S. and Song, S., 2006, 'Modeling for Predicting Frosting Behavior of a Fintube Heat Exchanger,' Int. J. Heat Mass Transfer, Vol. 49, pp. 1472-1479 https://doi.org/10.1016/j.ijheatmasstransfer.2005.09.022
  4. Ameen, F. R., Coney, J. E. R. and Sheppard, C. G W., 1993, 'Experimental Study of Warm-air Defrosting of Heat-pump Evaporators,' Int. J. Refrigeration, Vol. 16(1), pp. 13-18 https://doi.org/10.1016/0140-7007(93)90015-Z
  5. Kaygusuz, K., 1994, 'Performance of an Air-to-air Heat Pump Under Frosting and Defrosting Conditions,' Applied Energy, Vol. 48, pp. 225-241 https://doi.org/10.1016/0306-2619(94)90012-4
  6. Miller, W. A., 1983, 'Frosting Experiments for a Heat Pump Having a One-row Spine-fin Outdoor Coil,' ASHRAE Journal - American Society of Heating Refrigerating and Air-Conditioning Engineers, Vol. 25(12), pp. 74-74
  7. Votsis, P. P., Tassou, S. A., Wilson, D. R. and Marquand, C. J., 1989, 'Investigation of the Performance of a Heat Pump Under Frosting and Defrosting Conditions,' Heat Recovery Systems & CHP 9(5), pp. 399-406 https://doi.org/10.1016/0890-4332(89)90142-7
  8. Martinez-Frias, J. and Aceves, S. M., 1999, 'Effects of Evaporator Frosting on the Performance of an Air-to-air Heat Pump,' Transactions of the ASME 121, pp. 60-65
  9. Tantakitti, C. and Howell, R. H., 1986, 'Air-to-air Heat Pumps Operating Under Frosting Conditions on the Outdoor Coil,' ASHRAE Transaction-American Society of Heating Refrigerating and Air-Conditioning Engineers, pp. 827-841
  10. Jhee, S., Lee, K. S. and Kim, W. S., 2002, 'The Effect of Surface Treatments on the Frosting/defrosting Behavior of a Fin-tube Heat Exchanger,' Int. J. Refrigeration, Vol. 25, No. 8, pp, 1047-1053 https://doi.org/10.1016/S0140-7007(02)00008-7
  11. Wang, C. C. and Chang, C. T., 1998, 'Heat and Mass Transfer for Plate and Tube Heat Exchangers, with and Without Hydrophilic Coating,' Int. J. of Heat and Mass Transfer, Vol. 41, pp. 3109-3120 https://doi.org/10.1016/S0017-9310(98)00060-X
  12. Wang, S. W. and Liu, Z. Y., 2005, 'A New Method for Preventing HP from Frosting,' Renewable Energy, 30, pp. 753-761 https://doi.org/10.1016/j.renene.2003.07.001
  13. Martinez-Frias, J. and Aceves, S. M., 1999, 'Modeling of a Heat Pump with Evaporator Air Dehumidification for Reduced Frost Formation,' Journal of Energy Resources Technology - Transactions of the ASME, 121(3), pp. 189-195 https://doi.org/10.1115/1.2795981
  14. Lee, K. S., Kim, W. S. and Lee, T. H., 1997, 'A ?One Dimensional Model for Frost Formation on a Cold Flat Surface,' Int. J. Heat Mass Transfer, Vol. 40, No. 18, pp. 4359-4365 https://doi.org/10.1016/S0017-9310(97)00074-4
  15. Yang, D.K., Kim, J.S.· and Lee, K.S., 2004, 'Modeling for Prediction of Frost Formation Phenomena on a Cold Plate,' Transactions of the ?KSME (B), Vol. 28, pp. 665~671 https://doi.org/10.3795/KSME-B.2004.28.6.665
  16. ASHRAE HANDBOOK, 1993, Fundamentals. ASHRAE Atlanta
  17. Yang, D. K. and Lee, K. S., 2004, 'Dimensionless Correlations of Frost Properties on a Cold Plate,' Int. J. Refrigeration, Vol. 27, pp. 89-96 https://doi.org/10.1016/S0140-7007(03)00118-X

Cited by

  1. Application of a water-heat storage system for the prevention of duplex defrost using an air-source heat pump vol.224, pp.1, 2010, https://doi.org/10.1243/09544089JPME266
  2. Application of ground-heat-source water thermal-storage with a heat-pump cooling and heating system vol.224, pp.1, 2010, https://doi.org/10.1243/09544089JPME288