Abstract
Higher requirement of advanced building design code and the development of construction technique have resulted in more thermal and air tight buildings. This has caused the sick building syndrome in a indoor air quality has been relatively getting worse. A new concept with a solar fresh air heating and electrostatic precipitator or called as STCC(Solar Transpired Collector and Cyclone) has been proposed to solve this IAQ issue. This paper describes the assessment study of STCC system under different outdoor airflow rates. The experiment was carried out under real condition with 30CMM STCC system test facility. Incense smoke was used to study the particle concentration decay trends under outdoor airflow rates 0CMM, 10CMM, 20CMM, 30CMM, with applied voltages of 5kV and 15kV for collecting and discharging electrodes of an Electrostatic Precipitator. Result shows that the particle decay increases by increasing the outdoor airflow rates. The collection efficiency, dust cleaning effectiveness(P) and application area calculation result comparisons have also been studied. This factors could be used to estimate how a dust of indoor air quality(IAQ) and removed for a building space with a STCC system.