GIS형 접지계의 분류율 산정에 관한 연구

A Study on The Shunting Rates Evaluation of GIS type Grounding Systems

  • 발행 : 2005.04.01

초록

The testing and evaluating shunting rates of operating substations have become difficult recently due to various factors including increased fault current, limited area of urban substations and construction of substations in mountain location. In this paper, we have analysed the computation and measurement method of shunting currents that be applied grounding system maintenance of power substations. Also, simple and detailed test methods using 70Hz current injection are explained. A computer program is developed for a study on the shunting properties such as grounding impedance and shunting rates of grounding current, and the simulation results are compared with the measurement data to prove validity and effectiveness of the program and measurement method under commercial operation of a GIS type model substation respectively.

키워드

참고문헌

  1. 한국전력공사, 변전설계기준-2602 접지계설계지침 (1968년 제정, 1984년 개정, 2000년 재개정)
  2. 전력연구원, 운전중인 변전소와 접지계통 진단기술 개발 연구보고서, 한국전력공사, pp.3-106
  3. J. MA and F. P. Dawalibi, 'Effects of Inductive Coupling Between Leads In Ground Impedance Measurements using the Fall-of-Potential Method', IEEE Transactions on Power Delivery, Vo1.14, No.1, pp. 266-271.1999 https://doi.org/10.1109/TDC.1999.755359
  4. 電氣說備工事技術硏究會 編, 接地工事 設計 地工 マニコァル(第2版), オ一ム社, pp.317-326. 昭和54年
  5. IEEE Std-80-2000, IEEE Guide for Safety in AC Substation Grounding, IEEE, pp.113-118, 2000
  6. IEEE Std-142-1991, IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems. IEEE, pp.71-95, 1972
  7. 高橋健顔, 接地技術入門, オ一ム社, pp.69-100, 1993
  8. 高橋健顔, 接地技術入門, オ一ム社, pp.157-180, 1993
  9. EPRI, Transmission Line Reference Book-345 [kV] and Above(Second Edition), Electric Power Research Institute, pp.643-665,1982
  10. P. R. Pillai, E. P. Dick, 'A Review on Testing and Evaluating Substation Grounding Systems', IEEE Transactions on Power Delivery, Vol. 7, No.1, pp.53-61, January, 1992 https://doi.org/10.1109/61.108889
  11. Hiroyuki Makino, Hirokazu Itakura, 'Study of Overhead Ground-wire Shunting Rates during Ground Failure, for 500[kV] Substation Ground System Design', IEEE Proceedings, pp. 994-999, 1999 https://doi.org/10.1109/PESW.1999.747334