Measurement of Indoor Air Quality for Ventilation with the Existence of Occupants in Schools

  • Shin Hee-Soo (Department of Mechanical Engineering, Pusan National University) ;
  • Lee Jai-Kwon (Department of Mechanical Engineering, Pusan National University) ;
  • Ahn Young-Chull (Department of Mechanical Engineering, Pusan National University) ;
  • Yeo Chang-Shin (Department of Mechanical Engineering, Pusan National University) ;
  • Byun Sang-Hyun (Department of Mechanical Engineering, Pusan National University) ;
  • Lee Jae-Keun (Department of Mechanical Engineering, Pusan National University) ;
  • Kang Tae-Wook (Air Conditioner Division, LG Electronics) ;
  • Lee Kam-Gyu (Air Conditioner Division, LG Electronics) ;
  • Park Hyo-Soon (Building Energy Research Team, Korea Institute of Energy Research (KIER))
  • Published : 2005.04.01

Abstract

This paper evaluates the performance of ventilation for the removal of indoor pollutants as a function of ventilation rate and the number of occupants in a test room and school classroom. An experimental apparatus consists of a test room, a tracer gas supply system, a gas detector, and a fan for ventilation air supply with a controller. The ventilation performance is evaluated in a step-down method based on ASTM Standard E741-83 using $CO_{2}$ gas as a tracer gas in the test room of 35 $m^{3}.$ For the ventilation air flow rate of 1.0 ACH, a recommended ventilation flow rate of Korea school standard for acceptable indoor air quality in the case of one person, CO_{2}$ gas concentration decreases up to $55{\%}$ within 50 minutes without occupancy and increases up to $75{\%}$ in the case of one occupant. Also indoor air quality at the school classroom is investigated experimentally.

Keywords

References

  1. American Society for Testing and Materials, 1983, 'E741-83, Standard Test Method for Determining Air Leakage Rate by Tracer Dilution,' Philadelphia, PA.
  2. Cheng, Y. S., 1998, 'Efficiency of a Portable Indoor Air Cleaner in Removing Pollens and Fungal Spores,' Aerosol Science and Technology, Vol.29, pp. 92-101 https://doi.org/10.1080/02786829808965554
  3. EPA, 2000, IAQ Tools for School
  4. Han, H. T., 1999, 'On the Definition of Ventilation Effectiveness,' Korea Journal of Air-Conditioning and Refrigeration Engineering, Vol. 28, No. 1, pp. 38-47
  5. Kim, W. S., Lee, J. H., Park, Y. M., Yoo, J. S. and Park, K. S., 2003, 'Development of Fast-Response Portable NDIR Analyzer Using Semiconductor Devices,' KSME International Journal, Vol. 17, No. 12, pp. 2099-2106
  6. Lee, J. K., Kang, T. W., Lee, K. G., Cho, M. C., Shin, J. H., Kim, S. C., Koo, J. H. and Lee, J. H., 2000, 'An Experimental Study of Ventilation Effectiveness in Mechanical Ventilation Systems Using a Tracer Gas Method,' KSME International Journal, Vol. 14, No. 11, pp. 1286-1295
  7. Lee, J. K., Ku, J. H., Han, J. G., Kang, T. W., Lee, K. G. and Cho, M. C, 2001, 'A study on Ventilation Effectiveness of Mixing and Displacement Ventilation Systems in the Non-isothermal Supply Using a Model Chamber,' Proceeding of the SAREK 2001 Summer Annual Conference; pp. 654
  8. Lee, S. C. and Chang, M., 1999, 'Indoor Air Quality Investigation at Five Classrooms,' Indoor Air Short Communication, No. 9, pp. 134-138 https://doi.org/10.1111/j.1600-0668.1999.t01-2-00008.x
  9. Wark, K. and Warner, C. F., 1981, Air Pollution, It's Origin and Control, New York, Harper-Collins