Analysis of Volatage and Current Waveform Distortion Characteristics at Office Buildings

사무용 빌딩에서의 전압 및 전류파형 왜곡특성 분석

  • 유재근 (한국전기안전공사 전기안전연구원) ;
  • 이상익 (한국전기안전공사 전기안전연구원) ;
  • 전정채 (한국전기안전공사 전기안전연구원) ;
  • 정종욱 (한국전기안전공사 전기안전연구원) ;
  • 임용배 (한국전기안전공사 전기안전연구원)
  • Published : 2005.01.01

Abstract

Nonlinear electronic loads used at office buildings distort the voltage and current waveform that cause the overheating of transformer losses, ELB(Electrical Leakage Breaker) tripping, and so on. This paper analyzed waveform distortion characteristics at several once buildings by comparing with magnitude of voltage and current harmonics, crest factor of voltage and current, phase voltage and current unbalance. As a consequence, severe current waveform distortion in phase and neutral line by harmonics and high current unbalance rates by unbalanced using of single loads among the three phases are investigated. The results of the study can be used in making decisions regarding reasonable and economical operating of loads at office buildings.

사무용 빌딩의 비선형 전자부하에 기인한 전압 및 전류파형의 왜곡은 중성선의 과열, 변압기 손실, 누전차단기 오동작 등을 야기 시킨다. 본 논문에서는 사무용 빌딩에서의 전압 및 전류 고조파의 크기, 전압 및 전류 파고율(Crest Factor : CF), 전압 및 전류 불평형 등을 비교함으로써 파형왜곡 특성을 분석하였다. 분석 결과, 고조파에 의한 상 및 중성선에서의 심각한 파형 왜곡 문제와 삼상에서의 단상 부하의 부적절한 분배로 인한 전류 불평형이 심한 빌딩이 조사되었다. 본 연구 결과는 사무용 빌딩에서 합리적이고 경제적인 부하운용을 위해 사용될 수 있을 것이다.

Keywords

References

  1. IEEE Task Force, 'Effects of harmonics on equipment', IEEE Trans. Power Delivery, Vol. 8, Apr. 1993, pp.672-680 https://doi.org/10.1109/61.216874
  2. IEEE Task Force, 'The effects of harmonics on power systems equipment and loads', IEEE Trans. Power Delivery, Vol. PAS-104, Sept. 1985, pp. 2555-2563
  3. 이상중 외 3명, '집적정보통신시설 고조파 분석 및 다상 효과 관찰', 한국조명.전기설비학회 학술대회지, 2002, pp. 133-138
  4. Don O. Koval, Fellow, IEEE and Clive Center, 'Power Quality Characteristics of Computer Loads', IEEE Trans. Inustry Application, Vol. 33, No. 3, May/June 1997
  5. 한국전기안전공사, '전기사용장소의 고조파 장해분석 연구', 1996
  6. IEEE Standard 519-1992, 'IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power systems'
  7. 관동전기보안협회, '고압 자가용 수용가의 고조파 장해.억제대책 사례 Q&A', 성안당, 2000
  8. J. Arrillaga, N. R. Watson and S. Chen, 'Power System Quality Assessment, WILEY', 2001
  9. Motors and Generators, ANSI/NEMA Standard MG1-1993
  10. EPRI Power Electronics Applications Center, 'Input performance of ASDs during supply voltage unbalance', Power quality testing network PQTN Brif No. 28, 1996
  11. IEEE Standard Test Procedure for Polyphase Induction Motors and Generators, IEEE Standrd 112, 1991
  12. T. H. Chen, 'Evaluation of line loss under load unbalance using the complex unbalance factor', EEE Proc.-Gener. Transm. Distrib., Vol. 142, No. 2, March 1995, pp. 173-178