Evaluation Technique for Linearity of Ratio Error of Instrument Transformer Comparator Using Voltage Transformer with Wide Range of Error Ratios

넓은 범위의 비오차를 갖는 전압변성기를 이용한 계기용 변성기 비교 측정 장치의 비오차 직선성 평가기술

  • Published : 2005.02.01

Abstract

Linearity of ratio error of instrument transformer comparator has been tested using wide ratio error voltage transformer(VT) with the ratio errors in the range of -3 % to 3 %. The technique is the method for evaluation of the linearity for instrument transformer comparator by comparing both the theoretical and experimental values in wide ratio error VT. The developed method has been successfully applied for calibration and correction in instrument transformer comparator belonging to industry.

Keywords

References

  1. 정재갑, 권성원. 김규태, 김명수, '외부부담이 전압변성기의 비오차와 위상각오차에 미치는 영향에 대한 연구' 대한전기학회지, vol. 53C, No. 3, pp. 137-142, 2004
  2. 계기용변성기, KSC 1706
  3. J. L. Settles, W. R. Farber, and E. E. Connor, 'The analytical and graphical determination of complete potential transformer characteristics' IEEE Trans. Power Apparatus and Systems, vol. 79, No. 51, pp. 1213-1218, 1961
  4. IEEE Standard Requirements for Instrument Transformers, American National Standards Institute, ANSI/IEEE vol. C57, No. 13, pp. 45-46, 1978