초록

This paper deals with the performance analysis of static compensator (STATCOM) based voltage regulator for self­excited induction generators (SEIGs) supplying balanced/unbalanced and linear/ non-linear loads. In practice, most of the loads are linear. But the presence of non-linear loads in some applications injects harmonics into the generating system. Because an SEIG is a weak isolated system, these harmonics have a great effect on its performance. Additionally, SEIG's offer poor voltage regulation and require an adjustable reactive power source to maintain a constant terminal voltage under a varying load. A three-phase insulated gate bipolar transistor (IGBT) based current controlled voltage source inverter (CC- VSI) known as STATCOM is used for harmonic elimination. It also provides the required reactive power an SEIG needs to maintain a constant terminal voltage under varying loads. A dynamic model of an SEIG-STATCOM system with the ability to simulate varying loads has been developed using a stationary d-q axes reference frame. This enables us to predict the behavior of the system under transient conditions. The simulated results show that by using a STATCOM based voltage regulator the SEIG terminal voltage can be maintained constant and free from harmonics under linear/non linear and balanced/unbalanced loads.

키워드

참고문헌

  1. S. S. Murthy, O. P. Malik and A. K. Tandon, 'Analysis of self-excited induction generator,' IEE Proc., Vol. 129, Pt. C, No. 6, pp. 260-265, November 1982
  2. S. S. Murthy, Bhim Singh, Sushma Gupta and B. M. Gulati, 'General steady state analysis of three-phase self-excited induction generator feeding three-phase unbalanced load/single-phase load for stand-alone applications,' IEE Proc.-Gener. Transm. Distrib., Vol. 150, No. 1, pp. 49-55, January 2003 https://doi.org/10.1049/ip-gtd:20030072
  3. C. Grantham, D. Sutanto and B. Mismail, 'Steady state and transient analysis of self-excited induction generator,' IEE Proc., Vol. 136, Pt. B. No.2, pp. 61-68, March 1989
  4. K. E. Hallenius, P. Vas and J. E. Brown, 'The analysis of saturated self-excited asynchronous generator,' IEEE Trans. on Energy Conversion, Vol. 6, No.2, pp. 336-341, June 1991 https://doi.org/10.1109/60.79641
  5. M. H. Salama and P. G. Holmes, 'Transient and steadystate load performance of a stand-alone self-excited induction generator,' lEE Proc. Electr. Power Appl. Vol. 143, No.1, pp. 50-58, January 1996
  6. L. Wang and R. Y. Deng, 'Transient performance of an isolated induction generator under unbalanced excitation capacitors,' IEEE Trans. on Energy Conversion, Vol. 14, No.4, pp. 887-893, Dec. 1999 https://doi.org/10.1109/60.815004
  7. S. K. Jain, J. D. Sharma and S. P. Singh, 'Transient performance of three-phase self-excited induction generator during balanced and unbalanced faults,' IEE Proc. Gener. Transm. Distrib., Vol. 149, No.1, pp. 50-57, January 2002 https://doi.org/10.1049/ip-gtd:20020007
  8. M. B. Brennen and A. Abbondati, 'Static exciter for induction generator,' IEEE Trans. on Industry Applications, Vol. 13, No.5, pp. 422-428,1977 https://doi.org/10.1109/TIA.1977.4503433
  9. R. K. Mishra, Bhim Singh and M. K. Vasantha, 'Voltage regulator for an isolated self-excited cage induction generator,' Electric Power System Research, Vol. 24, No. 1, pp. 75-83, July 1992 https://doi.org/10.1016/0378-7796(92)90073-A
  10. L. Shridhar, Bhim Singh and C. S. Jha, 'Transient analysis of the self regulated short shunt self excited induction generator,' IEEE Trans. on Energy Conversion, Vol. 10, No.2, pp. 261-267, June 1995 https://doi.org/10.1109/60.391891
  11. E. Larsen, N. Miller, S. Nilsson and S. Lindgren, 'Benefits of GTO-based compensation systems for electric utility applications,' IEEE Trans. on Power Delivery, Vol. 7, No. 4, pp. 2055-2064, October 1997
  12. C. Schauder and H. Mehta, 'Vector analysis and control of advanced static VAR compensator,' lEE Proc.-C, Vol. 140, No.4, pp.299-306, July 1993
  13. Bhim Singh and L. B. Shilpakar, 'Analysis ofa novel solid state voltage regulator for a self-excited induction generator,' lEE Proc. Gener. Transm. Distrib., Vol. 145, No.6, pp. 647-655, November 1998 https://doi.org/10.1049/ip-gtd:19982357
  14. M. S. Miranda, R. O. C. Lyra and S. R. Silva, 'An alternative isolated wind electric pumping system using induction machines,' IEEE Trans. on Energy Conversion, Vol. 14, No.4, pp. 1611-1616, December 1999 https://doi.org/10.1109/60.815113
  15. S. C. Kuo and L. Wang, 'Analysis ofvoitage control for a self-excited induction generator using a current-controlled voltage source inverter (CC-VSl),' lEE Proc. Gener. Transm. Distrib., Vol. 148, No.5, pp. 431-438, September 2001 https://doi.org/10.1049/ip-gtd:20010477