Infuences of Harmonic Current on Electrical Characteristics of an Induction Motor

유도전동기의 전기적 특성에 미치는 고조파 전류의 영향

  • Park Yang-Birm (Department of Electrical Engineering, Cheongju Polytechnic College) ;
  • Kim Doo-Hyun (Department of Safety Engineering, Chungbuk National University)
  • Published : 2005.06.01

Abstract

This paper proposes the influences of harmonic current on electrical characteristics of an induction motor. Recently, a power system gets more worse as nonlinear load makes harmonics to affect energy lose of system and shorten lift of machines. In this paper, the electrical effect and THD(Total Harmonic Distortion) of harmonic current to an induction motor which is of great use in the industrial fields are measured and analyzed. A power conversion equipment(inverter) is installed to produce harmonics and variable reactors are installed to reduce the harmonics having an effect on the input terminal. Then the effects of the reactors are measured and analyzed. Also average voltage, current, power and 110 by harmonics are analyzed. The results show that Inn is increased by increasing load of the induction motor and installing reactors. And the harmonics affecting the input terminal are decreased by increasing reactor 3[mH] to 6[mH], however, average power of the induction motor is decreased. Therefore, it is very important that reactors should be carefully installed considering the merits and demerits resulting from the installation of reactors.

Keywords

References

  1. 김은식 외 1, 전력계통의 고조파 장해 분석, 한국전기안전공사, pp. 91-146
  2. 한국산업기술센터, 전기설비 운용 및 관리, pp.119-133, 2003. 6
  3. 강창원 외 4명, '전력계통에서의 고조파 개선 사례 연구', 대한전기학회 2000년 하계학술대회,pp. 224-227
  4. G.T. Heydt, Electric Power Quality, second Edition, Stars in a Circle Publications, Scottsdale(A/Z),u.s.a, 1994
  5. Mark McGranaghan, 'Overview of the Guide for Applying Harmonic Limits on Power Systems', IEEE P519A Draft6, 1996
  6. 'IEEE Recomended Practice and Requirements for Harmonics Control in Electrical Power Systems', IEEE Std. 519-1992