Precise Measurement of High Current Shunt Resistance

대전류 분류기 저항의 정밀측정

  • Published : 2005.09.01

Abstract

Precise measurement of extremely low resistance shunt is important for characterization and calibration of high current instruments. We tested resistance measurement method for extremely high current shunt (up to 140 kA), where resistance is determined by precise measurement of voltage drop at 10 A test current in the frequency range of 40 Hz to 10 kHz. For the extremely low ac voltage to be precisely measured, a verification of the measurement method was also carried, where the inherent noise is systematically evaluated. The measurement uncertainty was estimated to be $1\;\%\;at\;95\;\%$ confidence level (k=2) for about 50 $\mu\Omega$.

Keywords

References

  1. 국제단위계, 제7 개정판, KRISS-99-101-SP,1999
  2. 정주영 외, '대전류 표준측정시스템의 최종방안의 기술적 배경에 대한 고찰', 2003년도 대한전기학회 전력기술 부문회 추계학술대회 논문집, 2003.11
  3. ISO 'Guide to the expression of uncertainty in measurements,' 1991
  4. Agilent Application Note AN 1389-3, 'AC Voltage Measurement Errors in Digital Multimeters'