Comparison of Voltage Unbalance Factor for Line and Phase Voltage

선간전압과 상전압에 대한 전압불평형율의 비교

  • Published : 2005.09.01

Abstract

Most of the loads in industrial power distribution systems are balanced and connected to three power systems. However, voltage unbalance is generated at the user's 3-phase 4-wire distribution systems with single & three phase. Voltage unbalance is mainly affected by load system rather than power system. Unbalanced voltage will draws a highly unbalanced current and results in the temperature rise and the low output characteristics at the machine. It is necessary to analyse correct voltage unbalance factor for reduction of side effects in the industrial sites. Voltage unbalance is usually defined by the maximum percent deviation of voltages from their average value, by the method of symmetric components or by the expression in a more user-friendly form which requires only the three line voltage readings. If the neutral point is moved by the unbalanced load at the 3-phase 4-wire system. Line and phase voltage unbalance leads to different results due to zero-sequence component. So that it is difficult to analyse voltage unbalance factor by the conventional analytical method, This paper presents a new analytical method for phase and line voltage unbalance factor in 4-wire systems. Two methods indicate exact results.

Keywords

References

  1. 김종겸, 박영진, 정종호, 이은웅, '불평형 전압 운전시 유도전동기의 동작 특성 해석' 대한전기학회 논문지(B), 제 53권, 6호, pp.372-379, 2004.6
  2. 김종겸, 손홍관, 이은웅, '선형 및 비선형 부하량에 따른 고조파 성분의 변화' 대한전기학회 논문지(B), 제 51권, 8호, pp.441-448, 2002.8
  3. 김종겸, 박영진, 이은웅, '부하변동에 의한 전압불평형율의 특성 해석' 대한전기학회 논문지(P), 제 54권, 1호, pp.47-52, 2005.3
  4. 김종겸, 박영진, '3상 4선식 저압 수용가의 전압불평형율 측정 분석기', 한국조명전기설비학회 논문지, 제 18권, 6호, pp.91-99, 2004. 11 https://doi.org/10.5207/JIEIE.2004.18.6.091
  5. P. Pillay and M. Manyange, 'Definitions of voltage unbalance', IEEE Power Eng, Rev. Mag., vol.5, pp.50-51, May 2001 https://doi.org/10.1109/39.920965
  6. NEMA MG-1-2003, 'Motor and Generators'