Characteristics of Potential Gradient for the Type of Structure Grounding Electrode

구조체 접지전극의 유형에 따른 전위경도 특성

  • Published : 2005.08.01

Abstract

This paper Presents the Potential gradient characteristics of structure grounding electrode when a test current flows through grounding electrode. In order to analyze the potential gradient of ground surface on structure grounding electrode, the reduced scale model has been used. The potential gradient has been measured and analyzed for types of structure using the hemispherical grounding simulation system in real time. The structures were designed through reducing real buildings and fabricated with four types on a scale of one-one hundred sixty. The supporter was made to put up with weight of structure and could move into vertical, horizontal, rotary direction. When a test current flowed through structure grounding electrodes, ground potential rise was the lowest value at electric cage type(type B). According to resistivity and absorption percentage In concrete attached to structure, the potential distribution of ground surface appeared differently.

Keywords

References

  1. Chung-Seog Choi, Hyoung-Jun Gil, Hyang-Kon Kim, Woon-Ki Han, Bok-Hee Lee, 'Profiles of Ground Potential for Shapes of Grounding Electrode by Using Scale Model Grounding Simulation System', Progress in Safety Science and Technology, pp.104-112, 2004
  2. 길형준, 김향곤, 한운기, 이기연, 최충석, '축소모델을 이용한 봉형과 망상형 접지전극의 전위경도 비교', 한국안전학회 춘계학술발표회, pp.48-53, 2004
  3. Institute of Electrical Installation Engineers of Japan, 'Lightning Protection for Information-oriented and Computerized Society', IEIE of Japan, pp. 10-52, 1999
  4. A. Ohmi, 'Lightning Protection for Information and Telecommunication System', Journal of IEIE Jpn., Vol.21, No.6, pp.450-453, 2001
  5. IEC Pub. 1200-413, 'Electrical Installations Guide, Part413 ; Protection against Indirect Contact Automatic Disconnection of Supply', pp.9-19, 75-84, 1996
  6. IEC Pub. 364-413, 'Electrical Installations of Building, Part4 ; Protection for Safety, Chapter41 ;Protection against Electric Shock', pp.25-37, 1999
  7. 길형준, 최충석, 이복희, '반구형 접지모의시스뱀을 이 용한 접지전극의 형상에 따른 대지전위상승의 분석', 대한전기학회 논문지, Vol.54C, No.7, pp.319-325, 2005
  8. F. Dawalibi, D. Mukedkar, 'Optimum Design of Substation Grounding in a Earth Structure : Part I-Analytical Study', IEEE Trans. PAS., Vol.PAS-94, No.2, pp.252-261, 1975
  9. F. Dawalibi, D. Mukedkar, 'Optimum Design of Substation Grounding in a Earth Structure : Part II-Comparison between Theoretical and Experimental results',IEEE Trans. PAS., Vol.PAS-94, No.2, pp.262-266, 1975
  10. R. Cadecott, D.G. Kasten, 'Scale Model Studies of Station Grounding Grids', IEEE Trans. PAS., Vol.PAS-102, No.3, pp.558-566, 1975 https://doi.org/10.1109/TPAS.1983.317975
  11. B. Thapar, K. K. Puri, 'Mesh Potentials in High-Voltage Grounding Grids', IEEE Transactions on Power Apparatus and Systems, Vol.PAS-86, No.2, pp.249-254, 1967 https://doi.org/10.1109/TPAS.1967.291843
  12. Ronald P. O'Riley, 'Electrical grounding', Delmar Thomson Learning, pp.1-29, 2002
  13. 이복희,'접지의 핵심기초기술', 의제, pp.179-190, 2000
  14. IEEE Standards Board, 'ANSI/IEEE Std 80-1999; An American National Standard/IEEE Guide for Safety in AC Substation Grounding', The Institute of Electrical and Electronics Engineers, Inc., pp.31-48, 1986
  15. 이복희, 엄주홍, 김성원, '측정전류전이법을 이용한 운 전중인 접지시스템의 접지저항 측정', 대한전기학회 논문지 , VoI.51C, No.8, pp.347-353, 2002