Abstract
Study on the analysis of sodium spray fire using Gaussian drop size distribution, which redistributes a droplet spectrum with given mean diameter if its size classes with critical diameter(D>8mm) occur, was carried out. In this case, the oversized droplets were reduced to a stable diameter. Results calculated by the code using Gaussian drop size distribution were in better agreement with AI experimental results than those of NACOM and SPRAY code. The effect of variance on pressure in the test cell appeared greatly by introducing Gaussian function, which could represent various sodium droplet size distribution. The increase of the variance with mean droplet size resulted had an important effect upon the pressure in the test cell.