피뢰기 진단장치의 설계 및 제작

Design and Fabrication of a Lightning Arrester Analyzer

  • 길경석 (한국해양대 전기전자공학부) ;
  • 한주섭 (한국해양대 산업기술연구소) ;
  • 서황동 (한국해양대 전기전자공학부)
  • 발행 : 2004.11.01

초록

Various devices for diagnosing arrester soundness are suggested, and most of them simply measure magnitude of leakage current. However, such kind of devices do not provide detailed information needed for the diagnosis. In this study, we designed and fabricated a new arrester analyzer by means of measuring the magnitude, the phase vs. wave height and the harmonics of total leakage currents. The analyzer is composed of a current detector, an optical linker, and a main device operated by a microprocessor. The main device is connected with leakage current detector optically not to be influenced by electromagnetic interference. The analyzer developed measures only total leakage currents, but analyzes most parameters needed for the arrester diagnostics.

키워드

참고문헌

  1. S. Shirakawa, F. Endo, H. Kitajima, S. Kobayashi, K. Kurita, K. Goto, M. Sakai, 'Maintenance of surge arrester by a portable arrester leakage current detector', IEEE Transactions on Power Delivery, Vol. 3, No. 3, pp. 998-1003, 1988 https://doi.org/10.1109/61.193879
  2. J. Lundquist, L. Stensrom, A. Schei, B. Hansen, 'New method for measurement of the resistive leakage currents of metal-oxide surge arrester in service', IEEE Transaction on Power Delivery, Vol.5, No. 4, pp. 811-822, 1990
  3. S. Shichimiya, M. Yamaguchi, N. Furuse, M. Kobayashi and S. Ishibe, IEEE Trans. Pow. Deliv. 13, 465 (1998) https://doi.org/10.1109/61.660916
  4. 岡藤伸夫 外, '酸化亞鉛形避雷器の漏れ電流檢出方式の提案', 日本電氣學會電力.エネルギ一部門大會, pp. 850-851, 1994
  5. 石崎義弘 外, '避雷器の外部診斷技術', OHM, Vol. 74, No. 4, pp. 45-50, 1987
  6. 石?信治, '酸化亞鉛形避電器の劣化診斷テクニシク', 電氣計算, Vol. 55, No. 3, pp. 56-60, 1987
  7. 길경석, 한주섭, 송재용, 조한구, 한문섭, '누설전류의 파고분포 분석에 의한 새로운 피뢰기 진단기술 및 장치', 대한전기학회논문지, 52C권 12호, pp. 562-567, 2003
  8. 길경석, 한주섭, 김정배, '피뢰기 열화진단을 위한 저항분 누설전류의 측정장치', 대한전기학회논문지, 53C권 10호, pp. 469-475, 2003
  9. Hanxin Zhu, M.R.Raghuveer, 'Influence of Harmonics in Power System Voltage on Metal Oxide Surge Arrester Diagnostics', Proceeding of 1999 Conference on Electrical Insulation and Dielectric Phenomena, pp. 542-545, 1999 https://doi.org/10.1109/CEIDP.1999.807862
  10. 길경석, 한주섭, 주문노, '누설전류측정에 의한 피뢰기 열화진단에 있어 전원고조파의 영향', 대한전기학회논문지, 53C권 1호, pp. 41-46, 2003
  11. Agilent Technologies, HFBR-15x7/25x6-Versatile Link 125MBd Transmitters and Receivers, Datasheet for HFBR-0507 Series, Agilent Technologies Inc., 1999