A Study on the Analysis of Heat and Metallurgical Structure of Connection Parts for Residual Current Protective Devices

저압용 누전차단기 접속부의 발열 및 금속 조직 분석에 관한 연구

  • Published : 2004.12.01

Abstract

We investigated heat properties of connection terminal in residual current protective devices(RCD) according to contact pressure for low voltage appliance. And we analyzed voltage and current waveform and oxide propagation when the poor-contact happened between terminal and wire. When contact pressure between terminal and connection wire was not applied, the heat was generated and an oxide was formed on the surface of the wire. The temperature of the insulation surrounding terminal was ascended sharply by poor-contact, micro-sparks and continuous arc sound happened in interior terminal. When the poor-contact by vibration occurred inner conductor of terminal and wire, an oxide was propagated on contact surface and the temperature was increased at 869℃. Thus, we found that the risk of electrical disaster is high in terminal and connection wire parts.

본 연구에서는 저압용 누전차단기 접속단자에서의 접촉압력에 따른 발열특성을 조사하고 차단기 단자와 전선에 접촉 불량이 발생했을 때의 전압, 전류파형과 산화물 증식 등을 분석하였다. 차단기 단자와 전선에 접촉압력이 가해지지 않았을 때는 접촉저항증가로 열이 발생하고 금속표면에 산화 막이 형성되었다. 이때 단자 외부 절연물의 온도는 접촉 불량에 의해 급격하게 상승하며 단자내부에서 미세한 불꽃과 연속적인 방전음이 발생하였다. 단자내부도체와 접속전선 접촉면에서 기계적 진동에 의한 접촉 불량이 발생했을 때, 접촉면에서 산화물이 증식되고 발열온도는 869℃이상으로 상승하여 전기재해의 위험이 높음을 알 수 있었다.

Keywords

References

  1. 한국전기안전공사, '전기재해 통계분석', pp10-50(2003)
  2. 최충석, '전기화재공학', 동화기술, pp195-265(2004)
  3. 박용환, 양승용, '단면결함 전선에서의 화재발생메카니즘 연구', 한국화재소방학회 추계학술대회 논문집, pp61-67(2001)
  4. 김향곤 외 5, '접촉 압력에 따른 전선 연결기구의 열 특성 변화', 한국화재소방학회 춘계학술대회 논문집, pp127-132(2002)
  5. 原 英喜 외 1, '一般家庭におけ る低壓遮斷器接點の接觸抵抗とジュ.ル熱', J. IEIE Jan, 21(122), pp1031-1032(1995)
  6. 東京消防廳消防科學硏究室, '漏電遮斷等の電線接續部からの出火防止する硏空', フユスク, pp46-50(2001)
  7. Jarle sletbak, Roar Kristensen, Hakon Sundklakk, Gunnar Navik and Magne Runde, 'Glowing Contact Areas in Loose Copper Wire Connections', IEEE Trans. Comp., Hybrids, Manuf. Technol., 15(3), June. pp322-327(1992) https://doi.org/10.1109/33.148498
  8. Guo-Ping Lue, Jian-Gue Lu, and Ji-Gao Zhang, 'Failure Analysis on Bolt-type Power Connector's Application', IEEE, pp77-86(1999)
  9. Tamai, Aramata, 'Safe Levels of Silicone Contamination for Electrical Contact', Proceedings of the Thirty-Ninth IEEE Holm Conference on Electrical Contacts, pp269-273(1993)
  10. Maeda, Kinoshita, Yoshimura, Genma, 'Effects of Joints on Contact Reliability in Miniature Precision Snap-acting Switches', Proceedings of the ThirtySixth IEEE Holm Conference on Electrical Contacts, pp358-369(1990)
  11. 누전차단기 KS 규격(KS C 4613), 기술표준원(2003)