Evaluation Technique of Linearity of Ratio Error and Phase Angle Error of Voltage Transformer Comparison Measurement Equipment

전압변성기 비교 측정 장치의 비오차 및 위상각 오차의 직선성 평가기술

  • Published : 2004.09.01

Abstract

Both ratio error and phase angle error in voltage transformer(VT) depend on values of burden of VT used. A method of evaluation for linearity of ratio error and phase angle error in VT measurement equipment have been developed using the standard resistance burdens, with negligible AC-DC resistance difference less than $10^-6$. These burden consists of five standard resistors, with nominal resistance of 100 $\Omega$, 1 k$\Omega$, 10 k$\Omega$, 100 k$\Omega$, and 1 M$\Omega$. The developed method has been applied in VT measurement equipment of industry and the validity of the developed method has been verified by showing the consistency of the result of linearity obtained using VT with wide ratio error.

Keywords

References

  1. 계기용변성기, KSC 1706
  2. J. L. Settles, W. S. Farber, and E. E. Connor, 'The analytical and graphical determination of complete potential transformer characteristics', IEEE Trans. Power Applaratus and Systems, vol. 79, No. 51, pp. 1213-1218, 1961
  3. 정재갑, 권성원, 김규태, 김명수, '외부부담이 전압변성기의 비오차와 위상각오차에 미치는 영향에 대한 연구', 대한전기학회지, Vol. 53C, No. 3, pp. 137-142, 2004
  4. William E. Anderson 'A Calibration Service for Voltage Transfomers and High-Voltage Capacitors', NBS Measurement Services Special Publication 250-33, 1988
  5. Tinsley 'Precision Resistance Measurement', Tinsley Precision Instruments 1995