초록
In the paper, we summarize the result of the experimental research for the overload criteria of domestic distribution transformers considering the electric consumption patterns of customers. For the basic characteristic data of distribution transformer overload, the actual experiments are accomplished. The field data of loads are surveyed from sample transformers for analyzing the consumption pattern of customer load. The load data acquisition devices are equipped, and the algorithm of load pattern classification is applied. In addition to this efforts, various load pattern data. in past are gathered. Then the representative load pattern of each customer type in domestic is extracted. The final results of overload criterions are presented as tabular form through the results of experiments and survey are combined. The field test of the experiment results is peformed using the special manufactured transformers, which can measure both the load and top-oil temperature of transformer. Through this, we verify that the results of field test are similar to the laboratory one and the Proposed overload criteria can be effectively applied to the real system.