Abstract

Six stator slot couplers(SSC) and a flux probe sensor installed on the stator winding slots of large turbine generator. Assessment of insulation condition has been based upon the measurements of partial discharge(PD) of stator windings and shorted-turn of rotor windings in operating large turbine generator. The maximum PD magnitude(Qm), normalized quantify number(NQN), PD pattern and shorted-turn were measured using on-line insulation condition monitoring system. The NQN and Qm of slot PD side in the phase A are indicated the highest value in six SSC sensors. Monitoring system results showed that discharge at conductor surface and internal discharge were detected at the surface of stator winding and in voids of the groundwall insulation. Insulation of stator and rotor windings in large turbine generator was judged to be in good condition.

Keywords

References

  1. 김희동, '발전기 고정자 권선의 절연열화 메카니즘 분석', 한국전기전자재료학회 논문지, Vol. 15, No. 2, pp. 119-126, 2002 https://doi.org/10.4313/JKEM.2002.15.2.119
  2. 김희동, 주영호, '고압전동기 고정자 권선 절연재료의 미세구조 특성', 한국전기전자재료학회 춘계학술대회 논문집, pp. 513-517, 1999
  3. A. J. M. Pemen and J. W. Noteboom, 'Life Extension and Condition Monitoring of Generator', IERE Workshop, pp. 1-5, 1997
  4. G. Stone and J. Kapler, 'Stator Winding Monitoring', IEEE Industry Applications Magazine, pp. 15-20, 1998 https://doi.org/10.1109/2943.715501
  5. I. M. Culbert, H. Dhirani, and G. C. Stone, Handbook to assess the Insulation Condition of Large Rotating Machines, EPRI, EL-5036, Vol. 16, pp. 3-25-3-28, 5-13-5-14, 1989
  6. G. C. Stone, Partial Discharge Seminar, Iris Power Engineering Inc., Vol. 1, pp. 56-78, 2001
  7. D. R. Albright, Interturn Short-Circuit Detection, Generatortech. Inc., pp. 1-8, 1993