CAN 통신을 기반으로한 전력 시스템 자동화 구축

The Development of Power System Automation based on the CAN Communication Protocol

  • 박종찬 (오산대학 전기시스템제어과) ;
  • 김병진 (현대중공업(주) 기전연구소)
  • 투고 : 2003.04.15
  • 심사 : 2003.08.14
  • 발행 : 2003.09.01

초록

In this paper, the power system automation based on CAN communication protocol is introduced. Along with digitalization of electrical device, the various on-line services such as remote control, remote monitoring, remote parameter setting, fault data recording and remote diagnostic have been realized and become available. Therefore, it is necessary for those electrical devices to have real-time and reliable communication protocols. Author proposes DNPC(Distributed Network Protocol with CAN) which is proper to the power system SCADA (Supervisory Control And Data Acquisition) and DCS (Distributed Control System). The physical and datalink layer of DNPC protocol consists of the CAN2.0B which has the real-time characteristics and powerful error control scheme. As the transport and application layer, DNP3.0 is adopted because of its flexibility and compatible feature. Using the DNPC protocol, the power system automation is realized.

키워드