This study treats the analysis of the performance and the design of plume abatement wet/dry cooling tower with dry type heat exchanger using a numerical method. A two-dimensional analysis is performed using the finite volume method for mechanical draft counterflow and crossflow tower. For a coupling problem between water and air system, a turbulent two phase flow is considered. Effectiveness-NTU method is used for modeling of the dry type heat exchanger. The parameter change simulations of the outer wall shape, the relative flowrate of air, and attachment of an air mixer are performed to examine the effect on plume abatement. It is found that if the relative air flowrate ratio and the adequate air mixer type are chosen well in addition to the ratio of water to air flowrate, the loss of the cooling capacity and the additional cost are reduced and the plume is abated.

키워드

참고문헌

  1. Cooling Tower Institute Annual Meeting Control of fog from cooling towers Buss,J.R.
  2. Annual Meeting of the Cooling Tower Institute The prevention of fog from cooling tower Campbell,J.C.
  3. Cooling Tower Institute Annual Conference The new wet/dry cooling tower without finned tubedry section (NWD) Miura,T.;Gotoh,O
  4. Verein Deutscher Ingenieure v.70 Evaporative tooling, zeits Merkel,F.
  5. SAREK v.10 no.5 Numerical study for performance analysis and design of a counterflow type cooling tower Lee,S.Y.;Lee,J.H.;Choi,Y.K.;Ryou,H.S.
  6. Fundamentals of heat and mass transfer(4th ed.) Incropera,F.P.;DeWitt,D.P.
  7. ASME J. Heat Transfer v.105 no.4 Numerical modeling of wet cooling tower--Part 2 Majumdar,A.K.;Singhal,A.K.;Spalding,D.B.
  8. ASME J. Heat Transfer v.105 no.4 Numerical modeling of wet cooling tower-Part 1 Majumdar,A.K.;Singhal,A.K.;Spalding,D.B.