Abstract
The Korea Electric Power Corporation (KEPCO) has installed an 80 MY A Unified Power Flow Controller (UPFC) at its 154㎸ 'Kang-Jin Substation in South Korea. The device, manufactured by Siemens & Hyusung, has been operational since October 2002. The Korea Electric Power Research Institute (KEPRI), a division of KEPCO was tasked to study operational strategies that could be employed for the UPFC and surrounding reactive support devices concerning problems of low voltages and overloads in the Mokpo & Gwangju areas. Particular apprehension surrounded the possibility of delay in the installation of a new 345㎸ transmission line from 2005 to beyond 2010. The studies were to specifically determine whether these problems could be eliminated by application of a UPFC. The analysis included determining the UPFC operating point under various conditions, investigations of the coordination between the UPFC and a HYDC line terminating in this area, and the design of a supplementary damping controller for the UFPC. This paper summarizes the results of those studies, demonstrating the dynamic characteristics of the operation of this UPFC operation in the Korean power system.