DOI QR코드

DOI QR Code

Protection Effects of Surge Protective Devices According to Types of system Groundings

전원계통의 접지방식에 따른 서지보호기의 보호효과

  • 이복희 (인하대학교 전자전기공학부) ;
  • 이동문 (인하대학교 대학원 전기공학부) ;
  • 강성만 (인하대학교 대학원 전기공학부) ;
  • 이수봉 (인하대학교 대학원 전기공학부)
  • Published : 2003.11.01

Abstract

Electronic equipments made from integrated circuits and small-sized semiconductors is protected by surge protective devices(SPDs) such as ZnO varistors, Zener diode and gas discharge tube from lightning overvoltages. However the clamping voltage of SPDs is greatly influenced by the method of installing the SPDs. In this paper, the protective effects of SPDs according to types of system groundings were experimentally investigated. The separate grounding is a particularly undesirable way to install SPDs. The effectiveness of the common grounding point for ZnO varistors is more pronounced than that for gas discharge tubes. The common grounding at the terminal of SPDs is recommended as a best method of installing SPDs.

소형의 반도체와 회로로 구성되어진 전자기기는 뇌과전압으로부터 ZnO 바리스터, 지너다이오드, 가스방전관과 같은 서지보호장치 (SPDs)에 의해 보호되고 있다. 그러나 SPD의 제한전압은 SPD의 설치방법에 따라 커다란 영향을 받는다. 본 논문에서는 전원계통의 접지방식에 따른 SPD의 보호효과에 대하여 실험적으로 검토하였다. 독립접지는 SPD의 설치방법에 있어서 그다지 바람직하지 않다. 또한 가스방전관보다 ZnO 바리스터의 한 점을 공통접지하는 것이 더 효과적이다. SPD의 단자에 공통접지하는 것이 SPD의 설치방법에 있어서 가장 효과적임을 제안하였다.

Keywords

References

  1. B. Richter, “Surge Protective Devices for Low-Voltage Power Distribution Systems, -The New IEC-Standard and First Experience with It”, Proc. 23rd ICLP, Paper No.7C-1, pp.764-767, 1998.
  2. R. B. Standler, “”, John Wiley & Sons, Inc., First edition, New York, pp.3-33, 1989.
  3. 이복희, 이동문, 강성만, 엄주홍, 이승칠, “정보통신용 뇌서지 보호장치의 효과적인 설치기법”, 한국조명.설비학회 논문지, Vol.16, No.5, pp.90-96, 2002. https://doi.org/10.5207/JIEIE.2002.16.5.090
  4. M. B. Marz, S. R. Mendis, “Protecting load devices form the effects of low-side surges”, IEEE Trans., Vol. 29, No. 6, November/December 1993. https://doi.org/10.1109/28.259733
  5. Task Force Report, “Secondary(low-side) surge in distribution transformers”, IEEE Trans., Vol. 7, No 2, April 1992. https://doi.org/10.1109/61.127077
  6. IEC 61643-1, “Surge protective devices connected to low-voltage power distribution systems- Part 1 : Performance requirements and testing methods”, First edition, pp.3-37, 1998-02.
  7. IEC 61643-12, “Surge protective devices connected to low-voltage power distribution systems- Part 12 : Selection and application principles”, First edition, pp.113-117, 2002-02.
  8. T. Otsuka, K. Maezaki, “Experimental study of lightning surge current condition of low-voltage distribution line and house wire”, 電氣學會電力.エネルギ-部門大會, 電氣設備學會, pp.21-27, 1998