Insulation Test for the 22.9 kV Class HTS Power Transmission Cable

  • J.W. Cho (Korea Electrotechnology Research Institute) ;
  • Kim, H.J. (Korea Electrotechnology Research Institute) ;
  • K.C. Seong (Korea Electrotechnology Research Institute) ;
  • H.M. Jang (LG Cable Ltd., Electric Power R&D Center) ;
  • Kim, D.W. (LG Cable Ltd., Electric Power R&D Center) ;
  • Kim, S.H. (Gyeongsang National University and Engineering Research Institute)
  • Published : 2003.11.01

Abstract

HTS power transmission cable is expected to transport large electric power with a compact size. We are developing a 3-core, 22.9 kV, 50 MVA class HTS power cable, and each core consists of a conductor and shield wound with Bi-2223 tapes, electrical insulation with laminated polypropylene paper (LPP) impregnated with liquid nitrogen. This paper describes the design and experimental results of the model cable for the 22.9 kV, 50 MVA class HTS power transmission cable. The model cable was used the SUS tapes instead of HTS tapes because of testing the electrical characteristics only. The model cable was 1.3 m long and electrical insulation thickness was 4.5 mm. The model cable was evaluated the partial discharge (PD), AC and Impulse withstand voltage in liquid nitrogen. The AC and Impulse withstands voltage and PD inception stress was satisfied with the standard of Korea Electric Power Corporation (KEPCO) in the test results. The 3-core 22.9 kV, 50 MVA class HTS power cable has been designed and manufactured based on these experimental results.

Keywords

References

  1. Supercond. Sci. Technol v.13 HTS prototype for power transmission cable: recent results and future programs M.Nassi
  2. Cryogenic Eng. v.63 Outline of Verification Tests on a Superconducting Cable System for Practical Use S.Honju;Y.Takahashi
  3. Physica C v.354 High temperature superconducting cable field demonstration at Dtroit Edison N.Steve et al
  4. Korea-Japan joint Workshop 2002 on Applied Superconductivity and Cryogenics Effert of Winding Direction on 4-layer HTS Power Transmission Cble S.W.Kim et al
  5. Korea-Japan joint Worshop 2002 on Applied Superconductivity and Cryogenics Dielectric Characteristics of Insulating papers for HTS Cable S.H.Kim et al
  6. 2002joint Conference of ACED & K-J Symposium on ED and HVE Study on the Electrical Charanteristics of the liquid nitrogen/Paler Composite Insulation System for a HTS cable S.H.Kim et al