Verification of Controlled Closing Method for Unearthed Shunt Capacitor Banks by Simulation

비접지 분로 콘덴서 뱅크의 투입제어방식에 대한 시뮬레이션 검증

  • Published : 2003.09.01

Abstract

In this paper the controlled closing algorithm of the circuit breaker for isolated capacitor banks is proposed. The characteristics of circuit breakers such as RDDS(rate of decrease of dielectric strength) and a mechanical operating tolerance should be also taken into account to locate contact touch instants around voltage zero. The analysis results on the voltages across circuit breaker terminals upon closing operation play an important roles to describe the suggested method. The simulations carried out in order to verify the performance of this method show that the closing instants obtained from the proposed method provide a good suppression effect on the closing transients for both single and back-to-back capacitor banks.

Keywords

References

  1. H.Ito, 'Controlled switching technologies, State-of-the Art,' IEEE/PES Transmission and Distribution Conference Proceedings, Vol.2, pp. 1455-1460, Oct. 2002
  2. H.Tsutada, T.Hirai, H.Kohyama, H.lto, and K.Sasaki, 'Development of synchronous switching controller for gas circuit breaker,' IEEE/PES Transmission and Distribution Conference Proceedings, Vol.2, pp. 807-812, Oct. 2002 https://doi.org/10.1109/TDC.2002.1177579
  3. Task Force 13.00, 'Controlled switching - A state- of the art survey(part I),' ELECTRA, No. 162, pp 55-96, October 1995
  4. Task Force 13.00, 'Controlled switching - A state-of the-art survey(part II ),' ELECTRA, No. 164, pp 40-61, February 1996
  5. Working Group 13.07, 'Controlled switching of HVAC CBs guide for application lines, reactors, capacitors, transformers (1st Part),' ELECTRA, No. 183, pp,13-73, April 1999
  6. Working Group 13.07, 'Controlled switching of HVAC CBs guide for application lines, reactors, capacitors, transformers (2nd Part),' ELECTRA, No. 185, pp. 17-57, August 1999
  7. H.Hamada, A.Eto, T.Maekawa, etc., 'RDDS(Rate of Decrease of Dielectric Strength) Measurement for Gas Circuit Breaker, ,'IEEE/PES Transmission and Distribution Conference Proceedings, Vol.3, pp. 1755-1759, Oct. 2002 https://doi.org/10.1109/TDC.2002.1177720