Abstract

As tunnel ventilation has recently been playing a major role in the tunnel construction and maintenance, longitudinal ventilation systems with jet fans have been utilized a great deal because they are economical and effective. However, due to the length of tunnels and heavy traffic, it is hard to take the field measurements. In this study, therefore, the computer simulation and the model experiment of producing a wind tunnel were carried out simultaneously and the results were compared. The ultimate objective of this research was to interpret the air flow pattern inside the tunnel with a jet-fan was set up, and to offer the useful data for jet-fan installation and operation. The experiment was carried out with varying the jet-fan diameters, location of installation, the discharge velocity. Result showed that as the initial static pressure came up with the negative pressure, the tunnel air flowed into the inside of tunnel from outside due to the entrainment-effect and the backflow-phenomenon by separation-effect was observed in the lower half part of the tunnel. As the jet-fan was getting closer to the tunnel wall, the entrainment-effect caused by the interaction with the wall was increased; however, the mixing distance and irregular flow section became longer, and also the air pressure loss generated by wall friction was large.

Keywords

References

  1. Aerodynamics and Air Quality Management of Highway Tunnels Schlaug,R.N.;Carlin,T.J.
  2. Korean Journal of Air-Conditioning and Refrigeration Engineering v.28 no.6 Design and maintenance art of long tunnel Yoon,C.W.
  3. Korean Journal of Ait-Conditiong and Refrigeration Engineering A computational study on the longitudinal tunnel ventilation system Shin,H.J.;Kim,H.Y.
  4. Korean Journal of Air-Conditioning and Refrigeration Engineering Ventilation analysis according to jet fan location in long tunnel Ann,J.H.;Kim,J.S.;Kang,S.H.;Lee,J.H.
  5. Turbulent Jets Rajaratnam,N.
  6. Applied Fluid Dynamics Handbook Blevins,R.D.
  7. Engineering Fluid Mechanics(6th ed.) Roberson,J.A.;Crowe,C.T.
  8. 8th International Conference on Aerodynamics and Ventilation of Vehicle Tunnels An experimental study on the longitudinal ventilation system Martegani,A.D.;Pavesl,G.;Barbetta,C.
  9. Shock Losses Around Underground Overcast Tien,J.C.
  10. Proceedings of 7th US Mine Ventilation Symposium The entrainment pressure and flow process of a jet fan modeled in a square section wind tunnel Mutama,K.R.;Hall,A.E.
  11. ADC System Understanding of the Labview Graphic Program Jang,H.O.
  12. Fan Handbook Bleier,F.P.
  13. Basic Fluid Mechanics Gumin Shin,S.C.