디지털 스크롤 압축기를 적용한 시스템 에어컨의 냉난방특성에 대한 실험적 연구

Experimental Study on the Cooling and Heating Characteristics of System A/C Applying the Digital Scroll Compressor

  • 전용호 (선문대학교 기계공학과) ;
  • 김대훈 (선문대학교 기계공학과) ;
  • 권영철 (선문대학교 기계공학과) ;
  • 장근선 (선문대학교 기계공학과) ;
  • 이윤수 (공조기술연구센터) ;
  • 문제명 (삼성전자 시스템가전사업부) ;
  • 윤백 (삼성전자 시스템가전사업부) ;
  • 홍주태 (삼성전자 시스템가전사업부)
  • 발행 : 2003.06.01

초록

In order to investigate the cooling and heating characteristics of a variable-capacity system A/C applying a digital scroll compressor, the cooling and heating capacities and COP are measured by the psychrometric calorimeter. The capacity of the system is controlled by the digital scroll compressor, which is operated by controling PWM valve and the loading vs. unloading time. In the case of unloading compared that of loading, the consumption power of the compressor is about 11% and the capacity variation of the system A/C is within about 1%. When the system A/C is operated under the cooling and heating standard conditions, COP is nearly uniform but cooling capacity and heating capacity increase at minimum, rated and maximum modes. The system A/C applying the digital scroll compressor is effective for the range with high load or the width of large load variation. When the auxiliary heater is on, at the cold region, the system A/C produces the excellent heating capacity.

키워드

참고문헌

  1. Proc. of the DOE/ORNL Heat Pump Conference A comparative analysis of single and continuously variable-capacity heat pump concepts Rice,C.K.;Fisher,S.K.
  2. Refrigeration v.67 no.772 Multi air conditioner with two indoor unit Fujita,Y.;Kubo,T.;Suma,S.
  3. ASHRAE Transaction v.83 Factors affecting the performance of a residental air to air heat pump Parken,W.H.;Beausoliel,R.;Kelly,G.
  4. ASHRAE Journal New testing and rating procedures for seasonal performance of heat pumps Didon,D.A;Kelly,G.E.
  5. Proc. of the SAREK v.3 The experimental study on the comparison in performance of the system which used modulated compressors Kim,C.M.;Hwang,Y.J.;Ryu,Y.H.;Cho,K.S.
  6. Proc. of the SAREK v.3 Characteristics of oil flow pattern of DVM system(1) Seo,H.J.;Kim,J.M.;Lee,J.K.;Oh,S.K.;Moon,J.M.
  7. Finial Report Experimental study on the efficiency improvement of DVS system air-conditioner using the digital scroll compressor Kweon,Y.C.;Lee,Y.S.;Kim,D.H.;Jun,Y.H.
  8. Korean Agency for Technology and Standards. KS C 9306 Air conditioners
  9. ASHRAE Standard ANSI/ASHRAE 116-1983 Method of testing for seasonal efficiency of unitary air conditioners and heat pumps ASHRAE
  10. Proc. of the SAREK v.1 The effects of capacity modulation on the performance of residential vapor compression systems Ryu,Y.H.;Hwang,Y.J.;Kim,C.M.;Cho,K.S.