A Dynamic Rating System for Power Cables (I) - Real Time CTM(Conductor Temperature Monitoring)

전력 케이블 실시간 허용전류산정 시스템에 관한 연구 (I) - 실시간 도체 온도 추정 시스템

  • Published : 2003.07.01

Abstract

The domestic needs for larger capability of power sources are increasing to cope with the expanding power load which results from the industrial developments & the progressed life style. In summer, the peak load is mainly due to the non-industrial reasons such as air-conditioners and other cooling equipments. To cover the concentrated peak load in stable, the power transmission lines should be more constructed and efficiently operated. The ampacity design of the underground cable system is generally following international standards such as IEC287, IEC60853 and JCS168 which regards the shape of 100% daily full power loads. It is not so efficient to neglect the real shapes of load curves generally below 60~70% of full load. The dynamic (real time) rating system tends to be used with the measured thermal parameters which make it possible to calculate the maximum ampacity within required periods. In this paper, the CTM(Conductor Temperature Monitoring) which is the base of dynamic rating systems for tunnel environment is proposed by a design of lumped thermal network ($\pi$-type thermal model) and distribution temperature sensor attached configuration, including the estimation results of its performances by load cycle test on 345kV single phase XLPE cable.

Keywords

References

  1. A.Edris, 'Development and Field Application of EPRI Dynamic Thermal Circuit Rating (DTCR) Technology', Final Report, pp15.7-15.11, August. 1999
  2. IEC60853-2, 'Calculation of the cyclic and emergency current rationg of cables', pp.63-65, 1989
  3. J.H. Neher, 'The Determination of Temperature Transients in Cable Sustems by means of an Analogue Computer', Trans., AIEE, vol.70, pt2, pp1361-1369, 1951
  4. G.J. Anders, 'Rating of Electric Power Cables', IEEE Press, p46, 1997
  5. G.J. Anders, et al, 'Power Cable Thermal Analysis with Consideration of Heat and Moisture Transfer in the Soil', IEEE Transactions on Power Delivery, Vol. 3, No. 4, pp.1280-1285, October, 1988 https://doi.org/10.1109/61.193921
  6. S.H.Nam, et al., 'Dynamic Rating System for XLPE Cable in Tunnel', 電力 .ェネルキ-郡,門大會 論文集, 分冊 B, no365, 8月, 2002年
  7. IEC287-1-1, 'Electric cables-calculation of the current rating, Part1: current rating equations (100% load factor) and calculation of losses, section 1 : general', pp.20-21, 1994