An Advanced Algorithm for Compensating the Secondary Current of CTs

개선된 변류기 2차 전류 보상 알고리즘

  • Published : 2003.07.01

Abstract

During a fault the remanent flux in a current transformer (CT) may cause severe saturation of its core. The resulting distortion in the secondary current could cause the mal-operation of a protection relay. This paper proposes an algorithm for compensating for the errors in the secondary current caused by CT saturation and the remanent flux. The algorithm compensates the distorted current irrespective of the level of the remanent flux. The second-difference function of the current is used to detect when the CT first starts to saturate. The negative value of the second-difference function at the start of saturation, which corresponds to the magnetizing current, is inserted into the magnetization curve to obtain the core flux at the instant. This value is then used as an initial flux to calculate the actual flux of the CT during the course of the fault with the secondary current. The magnetizing current is then estimated using the magnetization curve and the calculated flux value. The compensated secondary current can be estimated by adding the magnetizing current to the secondary current. Test results indicate that the algorithm can accurately compensate a severely distorted secondary current signal.

Keywords

References

  1. D. A. Bradley, C. B. Gray, and D. O'Killy, 'Transient compensation of current transformers,' IEEE Trans. on PAS, vol. 97, no. 4, July/August 1978, pp. 1264-1271 https://doi.org/10.1109/TPAS.1978.354609
  2. Y. C. Kang, J. K. Park, S. H. Kang, A. T. Jones, and R. K. Aggrwal, 'An Algorithm for Compensating Secondary Currents of Current Transformers,' IEEE Trans. on PWRD, vol. 12, no. 1, January 1997, pp. 116-124 https://doi.org/10.1109/61.568231
  3. S. H. Horowitz, and A. G. Phadke, Power System Relaying, Research Studies Press LTD. 1992
  4. M. Kezunovic, L. Kojovic, A. Abur, C. W. Fromen, and F. Phillips, 'Experimental Evaluation of EMTP-Based Current Transformer Models for Protective Relay Transient Study,' IEEE Trans. PWRD, vol. 9, no. 1, January 1994, pp. 405-413 https://doi.org/10.1109/61.277712
  5. IEC 44-6, International Standard Part 6, Current Transformers, 1996