Influence of Combustion Flame on Flashover Characteristics Due to Fire Occurrence

화재발생시 직류 플래시오버특성에 미치는 연소화염의 영향

  • Published : 2003.06.01

Abstract

In this paper, characteristics of the DC flashover voltage in the horizontal air gap of sphere-sphere/needle-needle electrode system were investigated when the combustion flame of paraffin oil was present between the two electrodes. The reduction characteristic of DC flashover voltage was discussed with the thermal ionization process, the relative air density and the deflection phenomena in the shape of flames that caused by the corona wind and Coulomb's force. As the results of an experimental investigation, It was found that the reduction characteristics of DC flashover voltages with flames were affected strongly by the flame deflection and the change of relative air density. It was also found that the thermal ionization phenomena were not important in the range of combustion flame temperature.

본 연구에서는 파라핀 연소화염을 사용하여 침대침 및 구대구 전극배치에서 직류전압을 인가하였을 때, 대기압 공기의 플래시오버특성, 인가전압의 크기 및 극성에 따른 화염의 형상변화, 고온 연소화염의 열전리현상 및 플래시오버 특성에 미치는 상대공기밀도의 영향 등에 대해 조사하였다. 실험결과, 연소화염이 존재하면, 대기압 공기의 플래시오버특성은 매우 큰 영향을 받고 있다. 이는 전극의 형태에 따라 코로나풍과 쿨롱력이 작용함으로써 화염의 형상변화와 요동이 일어나기 때문이다. 또한 고온화염으로 인한 주변 공기의 상대공기밀도의 저하로 인해 플래시오버 특성은 더욱 낮아지고 있으며, 연소화염에 대한 열전리의 영향은 크지 않는 것으로 나타났다.

Keywords

References

  1. 산불관련정보, '산림청 홈페이지', http://www.foa.go.kr:9100/webapp/plsql/fo9sr403
  2. 김인식, 하장호, '화재발생에 따른 연소화염이 공기의 절연내력에 미치는 영향', 한국화재소방학회 논문지, 제6권 제1호, pp.30-38(2002)
  3. J. R. Fonseca and A. L. Tan, 'Effects of Agricultural Fires on the Performance of Overhead Transmission Lines', IEEE Transactions on Power Delivery, Vol. 5, No.4, pp.687-693(1990) https://doi.org/10.1109/61.53071
  4. 김기욱, '전기관계법규', 동일출판사, pp.309-350, (2000)
  5. 정성계, 이덕출, '개정 신판 고전압공학', 도서출판 문운당, pp.56-57(1997)
  6. A. G. Gaydon and H. G. Wolfhard, 'Flames : Their Structure, Radiation and Temperature', 4th ed., Chapman and Hall, pp.340-372(1979)
  7. E. Kuffel and W. S. Zaengl, 'High Voltage Engineering Fundamentals', Pergamon Press, pp.311-335(1984)
  8. L. Paris and R. Cortina, 'Switching and Lighting Impulse Discharge Characteristics of Large Air Gaps and Long Insulator String', IEEE Trans. Power Apparatus and Systems, Vol. PAS 87, No. 4, pp.947-957(1968) https://doi.org/10.1109/TPAS.1968.292069
  9. L. Aicher, 'Variations in the Dielectric Strength of Air', Allis Chalmers Electrical Review, Third Quarter(1949)