Dynamic Characteristics of Water Hammer Arresters for Building Service Applications

  • Cha, Dong-Jin (Department of Building Service Engineering, Hanbat National University)
  • Published : 2003.03.01

Abstract

Dynamic characteristics of water hammer arresters installed in a building water supply system have been investigated numerically by utilizing a commercial code that employs the method of characteristics. Some preliminary results with those arrester models produced in this study agree well with the previously reported. Then, the arrester models have been incorporated into a water supply pipe system of a 59 $m^2$apartment unit constructed by a leading construction company, and their dynamic characteristics have been investigated, especially on the reduction in the water hammer pressure. It is found that the setting of the arresters in the pipe system, which is recommended by the company, may not be proper for reducing the pressure down below 1,082.0 kPa (10.0 kg$g_f$/$cm^2$) when quick-closure valves in the pipe system are closed within 30 ms at the static pressure of 542.6 kPa (4.5 kg$g_f$/$cm^2$). More arresters in the system may be required to meet pressure criteria stated on the related standards and codes.

Keywords

References

  1. Wylie, E. B. and Streeter, V. L., 1993, FluidTransients in Systems, Prentice Hall, Englewood Cliffs, pp. 2-9
  2. Plumbing and Drainage Institute, 1996, Water Hammer Arrester-Certification, Sizing, Placement and Reference Data, PDI WH 201
  3. American Society of Sanitary Engineering, Water Hammer Arresters, ASSE Standard, No. 1010, 1996
  4. American National Standards Institute, Water Hammer Arresters, ANSI A112.26.1, 1996
  5. Kim, Y. H., 1997, A discussion on market, testing standards and practical application of water hammer arresters, Air-conditioning and Refrigeration Engineering, Vol. 26, No. 5, pp. 345-353
  6. Lee, Y.-H., Yoo, J.-O., Park, H.-S. and Kim,Y.-H., 2000, The experimental study of water hammer by valve closure in water supply piping system, Korean Journal of Airconditioning and Refrigeration Engineering, Vol. 12, No. 7, pp. 697-702
  7. Han, H. and Kim, J. M., 1996, An experimental study on the effect of water hammer arresters and air chamber in a simple water piping system, Korean Journal of Air-conditioning and Refrigeration Engineering, Vol. 8, No. 1, pp. 37-44
  8. Lee, Y.-H. and Yoo, J.-O., 2000, A study on surge pressure absorption by water hammer arrester in water supply piping system, Korean Journal of Air-conditioning and Refrigeration Engineering, Vol. 12, No. 12, pp.1066-1072
  9. Kang, S. Y., Ryu, H. S. and Park, M. S., 1992, Design and performance prediction of an air chamber for reduction of water hammering, Korean Journal of Air-conditioning and Refrigeration Engineering, Vol. 4, No. 1, pp. 57-64
  10. Hwang, H. S., Lim, K. W., Lee, K. B., Cho, B. and Cha, D., 2000, Characteristics of the transient pressure in a building water supply system with an air chamber, Korean Journal of Air-conditioning and Refrigeration Engineering, Vol. 12, No. 8, pp. 782-790
  11. Korea National Housing Corporation, 1998, Specifications for Housing Projects-Vol. 5; Mechanical Equipments, Kimundang Publishing Co., Seoul
  12. Sioux Chief Engineering, 2001, www.siouxchief.com
  13. Thorley, A. R. D. and Tiley, C. H., 1987, Unsteady and transient flow of compressible fluids in pipelines-a review of theoretical and some experimental studies, Int. J. Heat & Fluid Flow, Vol. 8, No.1, pp. 3-14
  14. Flowmaster International Limited, 1995, Flowmaster2, Version 5.2, England