국내 송전 케이블 시스 순환전류 실측 및 분석

Measurement and Analysis of Sheath Circulating Current in Domestic Underground Transmission Cables

  • 발행 : 2003.04.01

초록

The use of underground transmission tables has continuously increased in densely inhabited urban and suburban area. Due to a increasing demand of underground cables, two or more circuits are installed in parallel for several kilometers. It, however, has not been realized that the sheath circulating current is generated in the system where a large number of cables are laid in the same route. In this paper, Author studied diversely the sheath circulating current on underground cables depending on the various length rate, the phase arrangement, and the grounding resistance of the sheath in the cross-bonded section. It was clear that very large circulating current is generated in cable systems due to unbalanced length rate and phase arrangement in the cross-bonded section.

키워드

참고문헌

  1. 전력연구원, '지중송전계통의 접지기술 정립에 관한 연구', 1998.1
  2. 정채균, 이종범, 강지원, 장태인, '지중송전계통에서 시스순환 전류 해석 및 저감방안', 대한전기학회 논문지, Vol. 50A, No. 11, pp. 537-545, NOV. 2001
  3. IEEE, 'IEEE Guide for the application of sheath-bonding Methods for single-conductor cables and calculation of induced voltages and currents in cable sheaths, ANSI/IEEE Std 575-1988
  4. H. Nakanishi, et al., 'A Study of Zero-sequence Current Induced in a Cable System', IEEE Trans. Power Delivery, Vol. 6, No. 4, pp. 1352-1358, OCT. 1991 https://doi.org/10.1109/61.97663
  5. Turan Gonen, 'Electric Power Transmission System Engineering Analysis and Design', 1988
  6. 한국전력공사 기술연구원, '지중선 임피던스 및 허용전류 계산 기법 연구', 1991