Wind farm interconnected with grid can supply the power into a power network not only the normal conditions, but also the fault conditions of distribution network. If the fault happened in the distribution power line with wind fm, the fault current level measured in a relaying point might be lower than that of distribution network without wind turbine generator due to the contribution of wind farm. Consequently, it may be difficult to detect the fault happened in the distribution network connected with wind generator This paper describes the effect of the interconnected wind turbine generators on protective relaying of distribution power lines and detection of the fault occurred in a power line network. Simulation results shows that the current level of fault happened in the power line with wind farm depends on the fault impedance, the fault location. the output of wind farm. and the load condition of distribution network.

Keywords

References

  1. Philip P. Barker, 0Robert W. de Mello, 'Determining the Impact of Distributed Generation on Power Systems: Part 1- Radial Distribution Systems.' IEEE, No. 0-7803-6420-1/00, 2000 https://doi.org/10.1109/PESS.2000.868775
  2. Thomas Ackermann, Goran Andersson, Lennart Soder, 'Electricity Market Regulations and their Impact on Distributed Generation.' IEEE, No. 0-7803-5902-X/00, 2000 https://doi.org/10.1109/DRPT.2000.855735
  3. W. J. S. Rogers, 'The Parallel Operation of Generating Plant within a Regional Electricity Companys Distribution Network.' IEE Colloquium on 'The Parallel Operation of Generating Plant within a Regional Electricity Companys Distribution Network.' Chester, UK, Feb. 1991, pp. 1-9
  4. Jiang Fan and S. K. Salman, 'The Effect of Integration of Wind Farms into Utility Network on Voltage Control Due to the Co-ordination of AVC Relays.' Proceeding of the 4th International Conference on Advances in Power System Control, Operation and Management, APSCOM-97, Hong Kong, November 1997
  5. Salman K. Salman and Ibrahim M. Rida, 'Investing the Impact of Embedded Generation on Relay Settings of Utilities' Electrical Feeders.'IEEE Transactions on Power Delivery, vol. 9, No. 1, January 1994 https://doi.org/10.1109/61.915490
  6. A. F. Sultan, G. W. Swift, D. J. Fedirchuk, 'Detecting Arcing Downed-wires Using Fault Current Flicker and Half-cycle Asymmetry', IEE Trans. on Power Delivery, vol 9, No. 1, January 1994 https://doi.org/10.1109/61.277718
  7. 한국전력공사 계통운영처, '타사 발전기 병렬운전 연계 선로보호업무 지침' 1996. 8
  8. Manitoba HVDC Research Centre, ' EMTDC V3 User's Manual'
  9. 한국전력공사, '변전설비 현장 Guide Book', 2001
  10. R. J. Gustafson, R. pursley, V.D. Albertson, 'Seasonal Grounding Resistance Variations on Distribution Systems', IEEE Transacions on Power Delivery, vol.5, No.2, April 1990 https://doi.org/10.1109/61.53115