Journal of Korean Society on Water Environment (한국물환경학회지)
- Volume 18 Issue 3
- /
- Pages.327-336
- /
- 2002
- /
- 2289-0971(pISSN)
- /
- 2289-098X(eISSN)
Characteristics of Disinfection Performance in Water Treatment Plants with Introducing Treatment Technigue Requirement
정수 처리기술 기준 도입을 앞둔 전국 정수장의 소독능 관리 현황 및 특색
- Yeom, Cheolmin (Dept. of Environmental Eng., Ajou University) ;
- Cho, Soonhaing (Dept. of Environmental Eng., Ajou University) ;
- Jung, Haewoong (Samgoo Chemical Industry Co., Ltd.) ;
- Yoon, Jeyong (School of Chemical Eng., Seoul National University)
- Published : 2002.09.30
Abstract
Disinfection process in water treatment plants (WTPs) is one of the most important step in order to inactivate waterborne disease. However, what is the necessary disinfection in WTPs was not properly established in Korea. This study was conducted to evaluate disinfection performance in nationwide water treatment plants (n=474). Disinfection requirement based on the SWTR (Surface Water Treatment Rule) of the U.S. (1-log Giardia removal) was chosen in estimating the compliance. The scope of unit process for evaluating disinfection performance includes postdisinfection process in clearwells, pipeline, and storage tank. The worst water quality condition in individual WTPs was applied for the disinfection performance evaluation. The major results are as follows. First, it was appeared that 184 WTPs (39 %) provided insufficient disinfection performance. Disinfection performance was significantly improved during past 2 years. The ratio of the number of WTPs providing insufficient disinfection performance in 1999 and 2001 was 78 % and 41 %, respectively. One of major factors for this improvement was due to the improvement of