The Experimental Study on the Natural Ventilation Performance of Solar Chimney by the variation of Insulation Thickness and Height

단열재의 두께 및 연돌높이에 따른 태양열 굴뚝의 자연환기 성능에 관한 실험적 연구

  • Cho, S.W. (Department of Architectural Design, Samchok National University) ;
  • Kim, D.W. (Division of Architectural Engineering, Pukyong National University) ;
  • Im, Y.B. (Division of Architectural Engineering, Pukyong National University)
  • Published : 2002.09.30

Abstract

The results of experiment on the performance of natural ventilation by insulation thickness and height system of solar chimney are described. The 3-inside wall was made of concrete and 1-wall was made of glass. The two kinds of model experiment were performed. One was the varition of the 60cm, 90cm and 120cm of solar chimney, the other was the variation of the insulation thickness 10mm and 50mm and without insulation of outside wall of solar cimney. As the temperature difference between bottom and top expressed $1.7\sim2.9^{\circ}C$, air velocity measured $0.5\sim0.8m/s$ and ventilation rate was $194.4m^3/h$ in the case of the 120cm height of solar chimney, the respect of natural ventilation performance was superior to others cases in the first model experiment. Though the case of 120cm height of solar chimney was attached 50mm insulation the ventilation rate was not so much as the case of solar chimney was attached 10mm insulation. the temperature difference between bottom and top was the largest in the other cases. From this research, the natural ventilation performance of solar chimney was affected by not only height and insulation thickness of solar chimney but also wind velocity and directon.

Keywords

References

  1. 문보형, 조성우, 임영빈, 태양열굴뚝 높이에 따른 자연환기성능에 관한 연구, 대한건축학회부산경남지회 학술발표대회 논문집, 2001.11
  2. 유동우, 조성우, 임영빈, 태양열굴뚤의 단열재두께에 따른 자연환기성능에 관한 연구, 대한건축학회 부산경남지회 학술발표대회 논문집,2001.11
  3. H.B. Awbi, Ventilation of Buildings, E&FN SPON
  4. ASHRAE Fundamentals Handbook1993, chapter 23