수술실내 공기감염억제를 위한 공조용 급배기구 위치 선정에 관한 연구

A Study on the Diffuser Location for the Reduction of Airborne Infection in Operation Room

  • 권순정 (아주대학교 공과대학 건축학과) ;
  • 주영철 (순천향대학교 공과대학 기계공학과) ;
  • 김천숙 (순천향대학교 천안병원 마취과학교실)
  • 발행 : 2002.06.30

초록

The air ventilation system of operation rooms has been studied to prevent the cross infection during the operation. Operation rooms and air ventilation systems of three University hospitals were investigated. The distribution of microbe was measured by cultivating air samples in the operation room. A two-dimensional model for the cross-section of an operation room was developed for the CFD(Computational Fluid Dynamics) analysis. The characteristics of air flow in the empty operation room and in occupied operation room were calculated by using a CFD program. The current diffuser location of an old hospital did not deliver the clean air to the operation part efficiently. A new method to locate diffusers that improve air venting with little increase of the cost of equipment was suggested.

키워드