Performance Test of a R134a Centrifugal Water Chiller

  • 발행 : 2002.06.01

초록

A centrifugal water chiller using alternative refrigerant R134a has been developed. The prototype was designed to have refrigerating capacity of 300RT. Its compressor employs a single high-speed impeller, airfoil diffuser and collector. Newly developed, enhanced tubes were installed in the evaporator and the condenser to reduce the required head for the compressor. Off-design characteristics at various conditions, performance test of the compressor and analysis of the refrigeration cycle were performed. So the probability of use in part load condition was checked and the direction for revision was suggested.

키워드

참고문헌

  1. Lee, Y, Jeong, J, Kim, J. and Lee, C., 2000, Design of the Centrifugal Compressor for a R134a Turbo-Chiller, Proceedings of the SAREK 2000 Summer Annual Conference (II), pp. 435-442
  2. Japanese Association of Refrigeration and Japan Flon Gas Association, 1991, Thermo-physical Properties of Environmentally Ac-ceptible Fluorocarbons (HFC-134a and HCFC-123), Japanese Association of Refrigeration
  3. ASHRAE, 1996, Heating, Ventilating, and Air-Conditioning Systems and Equipment, Handbook 34-1996
  4. Air-conditioning and refrigeration institute, 1998, Standard for water chilling packages using the vapor compression cycle (Standard 550/590), p. 21
  5. LG Cable Ltd., 1999, Development of high performance heat exchanger (Turbo-B type evaporator/condenser), Ministry of Commerce, Industry and Energy