Analysis on Heat Supply Piping Network for Apartment House

아파트의 온수공급배관망해석

  • 박윤철 (제주대 기계에너지생산공학부) ;
  • 황광일 (삼성전자㈜ 시스템가전사업부)
  • Published : 2002.10.01

Abstract

The purpose of this research is to analyze the characteristics of flow rate distribution in hot-water piping networks in the apartment building. A 14-story apartment house was selected as a sample building and analyzed numerically by Hardy-Cross method. Two different piping networks, one has three vertical zones and the other of a single zone with automatic balancing valves, were compared. Some of research results are as follows; As the temperature of supply hot-water increases, the flow rate of it does by buoyancy effect, but this effect is not found in the piping network with automatic balancing valves. Non-uniformity in hot-water flow distributions to all stories in the piping system of single vertical zone can be completely reformed by the installation of either manually operated or automatic balancing valves in every story.

Keywords