Digital Relaying Algorithm for Power Transformer Protection using Fuzzy Logic Approach

  • Park, Chul-Won (Dept. of Electrical Engineering, Wonju National College) ;
  • Shin, Myong-Chul (School of Electrical & Computer Engineering, Sungkyunkwan University)
  • 발행 : 2002.04.01

초록

Power transformer protective relay should block the tripping during magnetizing inrush and rapidly operate the tripping during internal faults. Recently, the frequency environment of power system has been made more complicated and the quantity of 2nd frequency component in inrush state has been decreased because of the improvement of core steel. And then, traditional approaches will likely be maloperate in the case of magnetizing inrush with low second harmonic component and internal faults with high second harmonic component. This paper proposes a new relaying algorithm to enhance the fault detection sensitivities of conventional techniques by using a fuzzy logic approach. The proposed fuzzy based relaying algorithm consists of flux-differential current derivative curve, harmonic restraint, and percentage differential characteristic curve. The proposed relaying was tested with relaying signals obtained from EMTP simulation package and showed a fast and accurate trip operation.

키워드

참고문헌

  1. J. A. Sykes, I. F. Morrison, 'A Proposed Method of Harmonic Restraint Differential Protection of Transformers by Digital Computer', IEEE Trans. on PAS, Vol. PAS-91, No.3, pp.1266-I272, May/June 1972 https://doi.org/10.1109/TPAS.1972.293485
  2. The Institution of Electrical Engineers, Power System Protection, Vol. 3 Application: Electricity Association Services Limited., 1995
  3. M. A. Rahman, B. Jeyasurya, 'A State-of-art Review of Transformer Protection Algorithm' , IEEE Trans. on PWRD, Vol. 3, No.2, pp.534-544, April 1988
  4. Y. V. V. S Murty, W. J. Smolinski, 'Designed Implementation of a Digital Differential Relay for 3 Phase Power Trans former based on Kalman Filtering Theory', IEEE Trans. on PWRD, Vol. 3, No.2, April 1988
  5. M.A. Rahman, Y. V. V. S Murty, 'A Stand-alone Digital Protective Relay for Power Transformers', IEEE Trans. on PWRD, Vol. 6, No.1, pp. 85-95, Jan. 1991
  6. SJ. Lee, S.H. Kang, M.S. Choi, ST. Kim, S.H. Yoon and T.S. Lee, 'Protective Relaying Algorithm for 3 Phase Power Transformer Protection based on Fuzzy Decision Making' , KIEE International Trans. on Power Engineering, Vol. 12A, No.1, pp.26-30, March 2002
  7. Luis D. Periz, Alfred j. Flechsig, Jack L. Meador, Zoran Obradovic, 'Training an Artificial Neural Network to Discriminate between Magnetizing Inrush and Internal Faults', IEEE Trans. on PWRD, Vol. 9, No.1, pp.434-441, Jan. 1994
  8. A. Wiszniewski, B. Kasztenny, 'A Multi-Criteria Differential Transformer Relay Based on Fuzzy Logic', IEEE Trans. on PWRD, Vol. 10, No.4, pp.1786-1792, Oct. 1995
  9. B. Kasztenny, E. Rosolowski, 'A Self-organizing Fuzzy Logic based Protective Relay an Application to Power Transformer Protection', IEEE Trans. on PWRD, Vol. 12, No.3, pp.1119-1I27, July 1997
  10. Gomez-Morante, M. Nicoletti, D.W., 'A Wavelet-based Differential Transformer Protection', IEEE Trans. on PWRD, Vol. 14 Issue: 4, pp. 1351-1358, Oct. 1999
  11. A. G. Phadke, J. S. Thorp, 'A New Computer Relay Flux-restrained Current Differential Relay for Power Transformer Protection', IEEE Trans. on PAS, Vol. PAS-I02, No. 11, pp.3682-3629, Nov. 1983
  12. A. T. Johns, S. K. Salman, Digital Protection For Power Systems, IEE Power Series 15 : Peter Peregrinus Ltd. London, United Kingdom, 1995
  13. Chul-Won Park, H.S. Suh, Myong-Chul Shin, 'A Digital Protective Relaying using a Fuzzy Theory for Power Transformer Protection', in Proc. 1997 International Conference on ISAP'97, pp.269-273
  14. P. Bastard, P. Bertrand, M. Meunier, 'A Transformer Model for Winding Fault Studies', IEEE Trans. on PWRD, Vol. 9, No.2, pp.690-699, April 1994
  15. LEUVEN EMTP CENTER ATP Rule Book July 1987