DOI QR코드

DOI QR Code

에폭시/고무 거시계면에서 장시간 절연파괴전압에 대한 연구

Study on the Long Time Breakdown Voltage in the Macro Interface between Epoxy and Rubber

  • 발행 : 2002.11.01

초록

In this paper, the estimation of lifetime with the various conditions of the interface between toughened epoxy and rubber which are consisting materials of underground power delivery system has been studied. After the measurement of the short time AC interfacial breakdown strength on macro interfaces at room temperature, the breakdown time at several voltages were measured under the constant voltages lower than the short time breakdown voltage. The long time breakdown voltage was calculated by using Inverse Power Law. Two types of interfaces was studied. One was the interface between toughened epoxy and EPDM(Ethylene Prorylene Diene Terpolymer). The other was the interface between toughened epoxy and silicon rubber. Interfacial pressure and roughness of interfaces was determined through the characteristic of short time AC interfacial breakdown strength. Oil condition was no oiled, low viscosity oiled and high viscosity oiled. High viscosity oiled interface between Toughened epoxy and silicon rubber had the best lifetime exponent, 20.69. and the breakdown voltage of this interface after 30 years was evaluated 19.27㎸.

키워드

참고문헌

  1. IEEE Transactions on Power Delivery v.10 no.3 Development of prefabricated joint for 275-kV XLPE cable Yutaka Nakamishi;Akiharu Fukunaga;Sadao Fukunaga;Teruyoshi Tanabe;Masayuki Kobayashi;Nobio Shiseki;Ken'ichi Ando https://doi.org/10.1109/61.400890
  2. IEEE Trans. on Power Delivery v.11 no.2 Study on detection for the defects of XLPE cable lines Katsumi Uchida;Shin'ichi Kobayashi;Takao Kawashima;Hideo Tanaka;Susumu Sakuma;Ken'ichi Hirotsu;Hitoshi Inoue https://doi.org/10.1109/61.489320
  3. Conference Record of the 1994 IEEE International Symposium on Electrical Insulation Effect of pressure and length on interfacial breakdown between two dielectric surfaces D. Fournier;L. Lamarre
  4. Proc. 1999 Autumn Conf. KIEE Development of pre-mold joints for high voltage cable system S. K. Lee;E. K. Ko;Y. H. Kim;S. Y. Baik;K. S. Kim;G. D. Hun;W. K. Park
  5. ANSI/IEEE. Std. 930-1987 IEEE Guide for the Statistical Analysis of Electrical Insulation Voltage Endurance Data H. Rosen