Abstract

It is common to install multiple lines in the same route. Recently, excessive sheath circulating current was partially measured in underground cable systems of KEPCO. Especially, the installation type, unbalance section length between joint boxes and zero sequence current by distribution cable have an effect on the rising of sheath circulating current in the underground transmission system. If excessive current flows in sheath, sheath loss which is reduced the transmission capacity is produced. This paper describes the relation analysis of sheath circulating current and burying types. And also, a detailed analysis on rising cause and characteristic of sheath circulating current by considering various unbalanced conditions presents using analysis and measurement regarding cable systems which have the problem of excessive sheath circulation current.

Keywords

References

  1. 한국전력공사, '지중송전실무 I, II', 1996
  2. 전력연구원, '지중송전계통의 접지기술 정립에 관한 연구', 1998.1
  3. 정채균 외3, '지중송전계통에서 시스순환전류 해석 및 저감방안', 대한전기학회 논문지, Vol. 50A, No. 11, 2001
  4. IEEE, 'IEEE Guide for the application of sheath bonding Methods for single-conductor cables and calculation of induced voltages and currents in cable sheaths, ANSI/IEEE Std 575-1988
  5. J. S. Barrett, G. J. Anders, 'Circulating current and hysterisis losses in screens, sheaths, and armour of electric power cables-mathematical models and comparison with IEC Standard 287
  6. 강지원 외5, '지중 송전 케이블 계통에서 시스 순환전류 억제대책 검토', 2002년 전력케이블 연구회 심포지움 논문집, 2002
  7. M.G.Dwek, M.N.Eggleton, 'Electrical parameters of 400kV and 275kV cables used in England and Wales'
  8. 한국전력공사 기술연구원, '전력계통 과도해석 프로그램 이론 및 활용에 관한 연구', 1991
  9. 한국전력공사 기술연구원, '지중선 임피던스 및 허용전류계산 계산기법 연구', 1991
  10. Turan Gonen, 'Electrical power transmission system engineering', John Wiley & Sons