Performance Analysis of a Lowpass Filter on a CT Saturation Detection Algorithm

변류기 포화 판단 알고리즘의 저역통과 필터에 대한 성능 분석

  • Published : 2002.10.01

Abstract

A difference based current transformer (CT) saturation detection algorithm uses the third difference of a secondary current to detect the instants of the beginning/end of saturation. The third difference of a secondary current contains high frequency components when a CT is saturated. Thus, an effect of an anti-aliasing lowpass filter implemented in digital protection relays on the detection algorithm should be studied. This paper describes performance analysis of a lowpass filter on the CT saturation detection algorithm. The cutoff frequency of the lowpass filter is normally set to be half of a sampling frequency. In this Paper, two sampling frequencies of 3,840 (Hz) corresponding to 64 sample/cycle (s/c) and 1,920 (Hz) corresponding to 32 (s/c) are studied; the cutoff frequencies of the lowpass filters are set to be 1,920 (Hz), 960 (Hz) and 960(Hz), 480(Hz), respectively. And the proposed algorithm is verified by experiment. A 2nd order Butterworth filter is designed as a lowpass filter. The test results and experiment results clearly indicate that the saturation detection algorithm successfully detects the instants of the beginning/end of saturation even though a secondary current is filtered by the designed lowpass filters.

Keywords

References

  1. T.Bunyagul, P.Crossley, P.Gale, 'Overcurrent Protection Using Signals Derived from Saturated Measurement CTs', IEEE PES 2001 SM, July 15-19, 2001, Vancouver, BC, Canada https://doi.org/10.1109/PESS.2001.969993
  2. Y.C.Kang, J.K.Park, S.H.Kang, A.T.Johns, R.K.Aggarwal, 'An Algorithm for Compensating the Secondary Current of Current Transformers', IEEE Trans. on PWRD, Vol. 12, No. 3, January 1997, pp. 116-124 https://doi.org/10.1109/61.568231
  3. 강용철, 옥승훈, 강상희, '변류기 2차 전류의 포화 여부 판단 알고리즘', 대한전기학회논문지 A권, pp. 275-278, 제50권 제 6 호 2001년 6월