Fault Phase Selection Algorithm using Unit Vector of Sequence Voltages for Transmission Line Protection

대칭분 전압 단위 벡터를 이용한 송전선로 보호용 고장상 선택 알고리즘

  • Published : 2002.09.01

Abstract

A reliable fault phase selection algorithm plays a very important role in transmission line protection, Particularly in Extra High Voltage (EHV) networks. The conventional fault phase selection algorithm used the phase difference between positive and negative sequence current excluding load current. But, it is difficult to pick out only fault current since we can not know when a fault occurs and select the fault phase in weak-infeed conditions that dominate zero-sequence current in phase current. The proposed algorithm can select the accurately fault phase using the sum of unit vectors which are calculated by positive-sequence voltage and negative-sequence voltage.

Keywords

References

  1. ABB, 'REL521 User's Guide', 1996
  2. GE, 'DLP-Digital Line Protection', 1997
  3. B. Kasztenny, B. Campbell, J. Mazereeuw, 'Phase Selection for Single-Pole Tripping - Weak Infeed Conditions and Cross-Country Faults', 27th Western Protective Relay Conference, 2000
  4. Mitsubishi, 'Instruction Manual Digital Distance Relay Scheme Type MDT-F', Ver.F, 1999
  5. Toshiba, 'Numerical Distance Relay Type GRZ-100'
  6. Walter A. Elmore, 'Protective Relaying Theory and Applications'. Marcel Dekker, 1994
  7. J. Lewis Blackburn, 'Protective Relay Principles and Applications', Marcel Dekker, 1998
  8. GE, 'Single-Pole Tripping with SLYP-SLCN Relay System Description and Application'