Hybrid-Type Active Power Filters for Compensating Harmonic Current and Unbalanced Source Voltages

고조파 전류와 불평형 전원전압 보상을 위한 복합형 능동전력 필터

  • 이지명 (한국과학재단 신진연구원 연수과정) ;
  • 이동춘 (영남대학교 전자정보공학부)
  • Published : 2002.05.01

Abstract

In this paper, a novel control scheme compensating source voltage unbalance and harmonic currents for the combined system of series active and shunt passive power filter is proposed, where no low/high-pass filters are used in deriving the reference voltage for compensation. The phase angle and the reference voltages compensating for harmonic current and unbalanced voltage are derived from the positive sequence component of the unbalanced voltage set, which is simply obtained by using digital all-pass filters. In order to remove the phase delay in generating the reference voltage for compensation, the reference of 5th and 7th harmonic components is predicted one-sampling ahead. The validity of the proposed scheme has been verified for 3[kVA] proto-type active power filter system.

Keywords

References

  1. A. Campos, G. Joos, P. D. Ziogas, and J. F. Lindsay, 'Analysis and Design of a Series Voltage Unbalance Compensator Based on a Three-Phase VSI Operating with Unbalanced Switching Functions', IEEE Trans. on PE, vol. 9, no. 3, pp. 269-274, 1994 https://doi.org/10.1109/63.311259
  2. 목형수, 최규하, '3상 불평형 전원시스템의 새로운 위상각 검출기법을 이용한 순간전압보상기의 해석 및 제어,' 전력전자학회논문지, 제 4권, 제 3호, p275-283, 1999년 6월
  3. 정승기, 이동기, 박기원, '커패시터 필터를 갖는 3상 다이오드 정류회로의 불평형전원에서의 입력전류특성', 전력전자학회논문지, 제 6권, 제 4호, pp.348-361 2001
  4. H. Akagi, 'New Trends in Active Filters for Power Conditioning', IEEE Trans. on LA., vol. 32, no. 6, pp 1312-1322, 1996 https://doi.org/10.1109/28.556633
  5. L. Moran, I. Pastorini, J. Dixon and R. Wallace, n Series Active Power Filter Compensates Current Harmonics and Voltage Unbalance Simultaneously', IEE Proc.-Gener. Transm. Distrib., vol 147, no. 1, pp. 31-36, 2000 https://doi.org/10.1049/ip-gtd:20000027
  6. S. Srianthumrong, H. Fujita, and H. Akagi, 'Stability analysis of a series active filter integrated with a double-series diode rectifier,' IEEE Transactions on Power Electr., vol. 17, no. 1, pp. 117 124, 2002.S https://doi.org/10.1109/63.988677
  7. 우원명, 한윤석, 김영석, 원충연, 최세완, '직접보상전압추출기법을 이용한 새로운 직렬형 능동전력필터,' 전력전자학회논문지, 제 6권, 제 3호, pp.258-264, 2001
  8. F. Z. Peng and D. J. Adams, 'Harmonic Source and Filtering Approach,' IEEE IAS Conf. Rec., pp. 448-455, 1998
  9. H. Fujita and H. Akagi, 'The Unified Quality Conditioner: The Integration of Series- and Shunt-Active Filters,' IEEE Trans. on PE, vol. 13, no. 2, pp. 315-322, 1998 https://doi.org/10.1109/63.662847
  10. F. Z. Peng, H. Akagi, and A. Nabae, 'Compensation Characteristics of the Combined System of Shunt Passive and Series Active Filters', IEEE. Trans. on IA, vol. 29, no. 1, pp. 144-152, 1993 https://doi.org/10.1109/28.195900
  11. S. S. Lee, J. K. Kang, and S. K. Sui, 'A New Phase Detecting Method for Power Conversion Systems Considering Distorted Condition in Power System', IEEE IAS Conf. Rec., pp. 2167-2172, 1999 https://doi.org/10.1109/IAS.1999.798754
  12. Seung-Gi Jeong and Myoung-Ho Woo, 'DSP-Based Active Power Filter with Predictive Current Control', IEEE. Trans. on IE, vol. 44, no. 3, pp. 329-336, 1997 https://doi.org/10.1109/41.585830