초록
This paper was studied on the effect of temperature on corrosion of absorption refrigeration systems using $LiBr-H_2O$ working fluids. In the fresh water and 62 % lithium bromide solution at $70^{\circ}C$, polarization test of SS 400, Cu(C1220T-OL) and Al-Ni bronze was carried out. And polarization behavior, polarization resistance characteristics, corrosion rate(mmpy) and corrosion sensitivity of materials forming absorption refrigeration systems was considered. The main results are as following: (1) As the experimental temperature increase, the change of corrosion rate of Al-Ni bronze become duller than SS 400 and Cu in 62% lithium bromide solution. (2) According as corrosion environment is changed from fresh water to 62% lithium bromide solution, potential change of Cu and Al-Ni bronze become less noble than SS 400. (3) The corrosion sensitivity of Al-Ni bronze was duller than that of Cu and SS 400 in 62% LiBr solution.