Abstract
In this paper, characteristics of the ac and dc flashover voltage in the horizontal air gap of a needle-needle electrode system were investigated when the combustion flame was present near the high-voltage electrode. In order to examine the flashover phenomena and the corona inception voltages caused by flame we measured the voltage and current waveforms when the corona and the flashover was occurred. We also observed, as increasing the applied voltages, the deflection or fluctuation phenomena in the shape of flames caused by the corona wind and the coulomb's force. As the results of an experimental investigation, we found that the reduction of flashover voltages, in comparison with the no-flame case, are 62.7[%] for k=1.0, 34.2[%] for h=5[cm], 27.3[%] for h=7[cm] and 21.4[%] for h=9[cm] when ac voltage is applied.
본 연구에서는 불평등 전계인 침대침 갭을 수평배치하였을 때, 고전압 전극 부근에 설치한 화염에 의한 교류 및 직류 섬락전압 특성을 조사하였다. 화염에 의해 섬락이 발생할 때, 코로나 개시전압과 섬락극성을 조사하기 위해 전압 및 전류파형을 측정하였으며, 인가전압의 상승에 따른 코로나풍과 쿨롱력에 의한 화염의 형상이 왜곡되고 요동되는 현상을 관찰하였다. 실험 결과, 화염이 전극의 중간위치에 있을 때 화염에 의한 교류 섬락전압은 화염이 없는 경우에 비해 평균 62.7[%] 저하된 것으로 나타났으며, 화염의 높이에 따른 섬락전압의 특성에서 화염의 높이 h=5, h=7 및 h=9[cm]인 경우 교류 섬락전압의 평균값은 화염이 없을 때에 비해 각각 34.2[%], 27.3[%] 및 21.4[%] 저하된 것으로 나타났다.