Evaluation of Microfiltration Membrane as Prefilter for Reverse Osmosis membrane

역삼투막의 전처리를 위한 정밀여과막의 평가

  • hong, Seongho (Department of Chemical Environmental Engineering, Soongsil University) ;
  • Oh, Seoukhwan (Department of Chemical Environmental Engineering, Soongsil University) ;
  • Jeon, Jaehong (KOReD Co., Ltd., R&D Center)
  • 홍성호 (숭실대학교 환경.화학공학과) ;
  • 오석환 (숭실대학교 환경.화학공학과) ;
  • 전재홍 ((주)코레드 부설 연구소)
  • Published : 2001.09.01

Abstract

Some companies are trying to develop the microfiltration membranes because most of them used as a prefilter is imported in Korea. However, they are faced with much difficulty such as characterization of membrane and controlling of pore size on development. In this study, a microfiltration membrane developed by a company was evaluated for applicability to use as a prefilter before reverse osmosis membrane process in production of ultra pure water. The optimum feed pressure for the raw water was obtained at 0.2 to 0.4 atm. At that time, turbidity of the treated water was 0.4 NTU and flux was 6,000 to $9,000L/m^2/hr$. In case of the conventionally treated water, it showed the very stable flux and turbidity at 90% of recovery rate. The chemical cleaning was helpful to reduce the TMP for treated water. The turbidity was improved from 0.3 NTU to 0.1 NTU after chemical cleaning.

각종 전처리 필터로 사용되는 정밀여과막은 국내의 경우 대부분 수입에 의존하고 있다. 몇몇 회사에서 개발을 시도하고 있지만, 막에 대한 특성 파악이나 공극제어등과 같은 문제를 해결하는데 많은 어려움이 있다. 따라서 본 연구에서는 A 사에서 개발한 정밀여과막을 이용하여 한강원수와 시수에 대하여 RO 유입전 전처리 필터로서의 적합성을 판단하고자 본 연구를 수행하였다. 한강원수는 총 2회에 걸쳐서 실험을 실시하였다. 적정 공급수 압력은 0.2~0.4 기압이며 여과수의 탁도는 0.4 NTU를 나타냈다. 플럭스는 $6,000{\sim}9,000L/m^2/hr$ 였다. 시수의 경우 회수율을 90%로 운전시 안정된 플럭스와 탁도를 나타내었다. 화학세정 후 TMP의 증가율은 감소를 하였으며, 탁도는 0.4 NTU에서 0.1 NTU로 개선되었다.